Serial-DF1 properties

The
Configure RS-232 DF1 driver
dialog contains the following information.
Serial-DF1 properties
Setting
Description
Driver name
Specifies the name of the serial driver. If changed, the name must be unique across the entire topology and cannot exceed 255 characters.
COM Port
Lists the available COM ports on your computer. The driver transmits data to a device connected to the serial (COM) port of a computer. Select a port from the list. Available port numbers are from 0 through 31 (default is 1).
Device
Shows the DF1 device that is connected with your computer.
Baud rate
Specifies the baud rate for the driver that transmits data to your device. Available baud rates are 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200. The default is 19200.
Station number
Specifies the station number for the driver. Available station numbers are from 0 through 254 decimal (default is 0).
Parity
Matches the error-checking method for the connected driver (
None
,
Even
, or
Odd
).
Error check
Matches the setting of the device you are connected to (
BCC
or
CRC
). All devices on the network must be configured the same.
Stop bits
Specifies the amount of time between data transmissions. Basic DF1 protocol generally uses 1 (default is 1).
Protocol
Specifies the supported protocols (
Full Duplex
or
Half Duplex
).
Ack/poll timeout
Specifies the ACK value. The default is 3000 milliseconds.
Maximum retries
Specifies a value for the maximum number of times the system should retry. The default is 3.
Test configuration
Tests if the driver configuration is correct. Before testing, ensure that your DF1 device is connected.
If the test fails, possible reasons include:
  • The COM port is in use by
    RSLinx Classic
    or
    FactoryTalk® Linx
    .
  • CIP serial is not set as the driver.
  • The driver configuration does not match the connected driver.