2085-IF4 input variable ranges

The ranges for the input variables of the 2085-IF4 expansion module vary with the data format and input range you selected. The data format range for the 2085-IF4 expansion module covers the full analog ranges:
  • 0 mA to 20 mA is 0 mA to 21 mA
  • 4 mA to 20 mA is 3.2 mA to 21 mA
  • –10V to +10V is –10.5V to +10.5V
  • 0V to 10V is –0.5V to 10.5V
Data format selections for 2085-IF4 and the corresponding type and range
Data Format
Type/Range
0 mA to 20 mA
Type/Range
4 mA to 20 mA
Type/Range
–10V to +10V
Type/Range
0V to 10V
Raw/proportional data
–32768 to 32767
Engineering units
The resolution is 0.001V or 0.001 mA per count. For example, 9999 here means 9.999V or 9.999 mA (or 9999 x 0.001).
0 to +21000
+3200 to +21000
–10500 to +10500
–500 to +10500
Percent range
The resolution is 0.01% per count. For example, 9999 here means 99.99% (or 9999 x 0.01%).
0 to +10500
–500 to + 10625
Not supported
–500 to +10500