Add an expansion module to a controller project
Expansion I/O modules extend the capabilities of L50E and L70E controllers by optimizing the flexibility of the I/O count and type.
For L50E controllers:
- Add no more than four expansion modules.
- To avoid program compiling problems, limit the total number of digital inputs and outputs to:
- 192 or less for L50E controllers with 48 digital I/O points.
- 132 or less for other L50E controllers.
For L70E controllers:
- Add no more than eight expansion modules and no more than one power supply expansion module.
- To avoid program compiling problems, limit the total number of digital inputs and outputs to 304 or less.
To add an expansion module to a controller project
- InProject Organizer, go to .
- Right-clickExpansion, and then selectNew module.
- InAdd module, select an expansion module, and then selectAdd.
- InDevices definition, select the slot, revision, and controller fault behavior as needed, and then selectOK.