Ptxx view parameters - 5094-IB16(XT)

The
Ptxx
view includes these parameters:
Parameter
Description
Off -> On filter time
Defines how long an Off to On input transition must remain in the On state before the device considers the transition valid.
On -> Off filter time
Defines how long an On to Off input transition must remain in the Off state before the device considers the transition valid.
Enable timestamp latching
Determines whether timestamps are latched.
  • When enabled, the device timestamps will not be overwritten until acknowledged.
  • When disabled, the device timestamps may be overwritten.
Capture timestamp for:
Off -> On input transition
Determines whether a timestamp is recorded for the Off -> On input transition.
Capture timestamp for:
On -> Off input transition
Determines whether a timestamp is recorded for the On -> Off input transition.
Enable chatter detection
Sets chatter detection. When enabled, chatter from a device connected to one of its inputs (for example, rapid transitions from a failed contact) is ignored.
Chatter can cause the device to timestamp invalid input transitions. Typically, chattering signals cause inputs to transition falsely many times in a relatively short period of time.
Chatter count
Determines the number of acceptable input transitions that can occur in a given time period before considering the input to be chatter.
Valid values are from 2 through 127.
Chatter time
Determines the amount of time,from 1 to 10000 milliseconds, within which the number of input transitions are counted.