Points view parameters - 5094-OW8I(XT)

The
Points
view includes these parameters:
Parameter
Description
Point
Displays the point number to which this configuration applies.
Output State During
Program Mode
Determines the behavior of each output when the controller transitions to Program mode. While in Program mode, outputs from the controller are ignored and the output behaves according to these:
  • Off
    - Output is 0 or Off
  • On
    - Output is 1 or On
  • Hold
    - Output maintains last state
Output State During
Fault Mode
Determines what happens to the output of each point after a communication fault occurs and the device enters Communications Fault mode.
  • Off
    - Output is 0 or Off
  • On
    - Output is 1 or On
  • Hold
    - Output maintains the current level
Fault Mode Output State
Duration
Determines the length of time the Fault Value value is held prior to the Final Fault State.
Fault Mode Output State
Final State
Determines whether the device transitions to
On
or
Off
after the Fault Mode Output State Duration elapses. The default final state is
Off
. If you choose Forever for Duration, you cannot choose a final state. The device retains its current Fault mode state.
Output State When Communications Fail in Program Mode
Determines the output action if communication fails in Program Mode:
  • Program Mode
    - Indicates leaving outputs in Program mode.
  • Fault Mode
    - Indicates changing outputs to Fault mode.
Diagnostics
Opens the diagnostics dialog box to view diagnostics information.