Points view parameters - 5094-IM8(XT)

The
Points
view includes these parameters:
Parameter
Description
Point
Displays the point number to which this configuration applies.
Input Filter Time
Off -> On
Defines how long an Off to On input transition must remain in the On state before the device considers the transition valid.
Input Filter Time
On -> Off
Defines how long an On to Off input transition must remain in the Off state before the device considers the transition valid.
Enable Field Power Diagnostics
Determines whether the channel faults when no field power is present.
  • If the input is powered from the SA, select this check box to monitor the status of the SA power.
  • If the input is powered from another power supply, do not select this check box, so that the input continues to work even when there is no SA power.
Diagnostics
Opens the diagnostics dialog box to view diagnostics information.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal