Event0x view parameters - 5094-IB32(XT)

The
Event0x
view includes these parameters:
TIP:
The
Event0x
view is only supported on points 0...15. The
Event0x
view is not supported on points 16...31.
Parameter
Description
Member Name
Value
Enable event
Determines the corresponding event trigger definition to activate. Events are triggered once when conditions match the definition.
EO.Event0x.En
  • 0 = Event trigger definition is not active.
  • 1 = Event trigger definition is active.
Latch event
Determines whether an event is latched until it is acknowledged.
EO.Event0x.LatchEvent
  • 0 = Event is not latched. New events overwrite old events.
  • 1 = Event is latched. New events are lost if the latched event was not acknowledged.
Enable independent point triggers
Determines whether each condition indicated in the Event trigger definition can initiate an event independently.
EO.Event0x. IndependentConditionTriggerEn
  • 0 = When all selected conditions achieve the configured values an event is triggered.
  • 1 = When any selected condition achieves the configured value an event is triggered.
Trigger event
Triggers an event each time a condition change results in conditions:
  • matching the event trigger definition, or
  • no longer matching the event trigger definition.
EO.Event0x.EventRisingEn
EO.Event0x.EventFallingEn
When
Enable independent point triggers
is selected (EventRisingEn, EventFallingEn)
  • Disable (0,0)
  • On transition (1,0)
  • On inverted transition (0,1)
  • On any transition (1,1)
When
Enable independent point triggers
is cleared (EventRisingEn, EventFallingEn)
  • Disable (0, 0)
  • On input transition to match pattern (1, 0)
  • On input transition to not match pattern (0, 1)
  • On input transition to match or not match pattern (1, 1)
Participate in event trigger
Indicates that the specified point participates in the Event trigger definition for the event.
EO.Event0x.Pt0xDataSelect
  • 0 = Point does not participate in the Event trigger definition
  • 1 = Point participates in the Event trigger definition
State transition
Determines whether the specified point transitions after the event.
EO.Event0x.Pt0xDataValue
If
Enable independent point triggers
is cleared:
  • 0 = Off
  • 1 = On
If
Enable independent point triggers
is selected:
  • 0 = Off -> On
  • 1 = On -> Off
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal