Tag definitions (5034-IA8)

The 5034-IA8 modules have configuration and input tags.
Configuration Tags
Name
Data Type
Definition
Valid Values
Ptxx.InputOffOnFilter
SINT
The amount of time that a signal must be in the On state before the input data indicates the On state.
The amount of time is indicated using an enumeration.
  • 13 = 1 ms
  • 14 = 2 ms
  • 15 = 5 ms
NOTE: For a module operating with a 120V AC input signal, the only valid Off to On filter value is 1 ms.
Ptxx.InputOnOffFilter
SINT
The amount of time that a signal must be in the Off state before the input data indicates the Off state.
The amount of time is indicated using an enumeration.
  • 16 = 10 ms
  • 17 = 20 ms
Input Tags
Name
Data Type
Definition
Valid Values
RunMode
BOOL
The module's operating state
  • 0 = Idle – It means one of the following:
    • Connection is not up.
    • Connection has been opened but the module has not started producing data for the connection.
  • 1 = Run – It means the following:
    • Connection is up.
    • Module is producing data for the connection.
ConnectionFaulted
BOOL
Indicates if a connection to the target is running.
The module always returns a zero in this member. The controller overwrites the zero with a one when the connection is not up.
  • 0 = Connection is running.
  • 1 = Connection is not running.
DiagnosticActive
BOOL
Indicates if any diagnostics are active or if the prognostics threshold is reached.
  • 0 = No diagnostics are active.
  • 1 = One or more diagnostics are active or the prognostics threshold is reached.
Uncertain (Packed data)
BOOL
Indicates that the point data can be inaccurate but the degree of inaccuracy is not known.
If the tag is set to 1, you must troubleshoot the module.
  • 0 = Good data
  • 1 = Uncertain data
DiagnosticSequenceCount
SINT
Increments for each time a distinct diagnostic condition is detected, and when a distinct diagnostic condition transitions from detected to not detected.
-128…+127
The value of 0 is skipped except during module powerup.
Ptxx.Data
PtxxData (Packed data)
BOOL
Indicates the current digital input value.
  • 0 = Off
  • 1 = On
Data (Packed data)
INT
Indicates the current values for all points of the module. Each bit represents 1 point. For example, Bit.3 represents the Data of Pt03.
For each point:
  • 0 = Off
  • 1 = On
Ptxx.Fault
PtxxFault (Packed data)
BOOL
Indicates that point data is inaccurate and cannot be trusted for use in the application.
If the tag is set to 1, you must troubleshoot the module to correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes the tag to change to 1 is removed, the tag automatically resets to 0.
  • 0 = Good
  • 1 = Bad, causing fault
Fault (Packed data)
INT
Indicates the fault state for all points of the module. Each bit represents 1 point. For example, Bit.3 represents Fault status of Pt03.
Fault state indicates that point data is inaccurate and cannot be trusted for use in the application.
If the tag is set to 1, you must troubleshoot the module to correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes the tag to change to 1 is removed, the tag automatically resets to 0.
For each point:
  • 0 = Good
  • 1 = Bad, causing fault
Ptxx.Uncertain
BOOL
Indicates that the point data can be inaccurate but the degree of inaccuracy is not known.
If the tag is set to 1, you must troubleshoot the module to correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes the tag to change to 1 is removed, the tag automatically resets to 0.
  • 0 = Good data
  • 1 = Uncertain data