Counters view parameters (5034-IB16, 5034-IB8)

The
Counters
view includes these parameters:
Parameter
Description
Counter
Displays the counter number to which this configuration applies.
Input Filter Time
Off → On
Defines how long an Off to On input transition must remain in the On state before the device considers the transition valid.
Input Filter Time
On → Off
Defines how long an On to Off input transition must remain in the Off state before the device considers the transition valid.
Preset
Displays the value, set in the output tag Preset, to use for counter preset. The value can range from 0…2,147,483,647.
Rollover at Preset
Determines the action that is taken when the input tag Count reaches the Preset value.
  • If selected, the counter counts to the Preset value, rolls over to zero, and then sets the Rollover bit. The Done bit is not set.
  • If cleared, the counter counts to the Preset value and sets the Done bit, then continues counting up to the maximum DINT value. The Rollover is set when Count transitions from 2,147,483,647 to 0.
Diagnostics
Opens the Diagnostics dialog, which contains diagnostic information.