Scaling to engineering units in input devices
Channel data values in the input tag may be in engineering units such as Bar, Degrees Celsius, Kg/minute or percentage. To configure the relationship between the physical signal in volts or mA and engineering units, set the
Low
and High Signal
and the Low
and High Engineering
values.For example, a temperature transmitter on channel 3 which produces 4 mA current at -180 degrees C and 20 mA of current at 750 degrees C, and you are using Degrees C in your control program, configure the values as in this table.
Setting | Signal | Engineering |
|---|---|---|
High | 20 | 750 |
Low | 4 | -180 |
If you are using HART field devices, we recommend setting
High Engineering
and Low Engineering
to the field device’s Upper Range Value
and Lower Range Value
so that the field device uses the same engineering units as the 1756-IF8H. If online, these values display in HART Device Information