Device filter
The
Device filter
setting allows configuration of the 3dB frequency of the filter in the A/D converters. This selection affects the -3dB frequency, the 50 Hz rejection, the 60 Hz rejection, the effective resolution, and the minimum sample time (RTS) as shown in the following table. This table is for information purposes only:
TIP:
The effective resolution is over a current range of 0-21 mA and applies to both the 0-20 mA and 4-20 mA range configuration settings.
Device Filter Selection 1 | 15 Hz | 20 Hz | 50 Hz | 60 Hz | 100 Hz | 250 Hz | 1000 Hz |
|---|---|---|---|---|---|---|---|
Channel ADC Update Rate 1 | 50 SPS | 60 SPS | 150 SPS | 150 SPS | 300 SPS | 960 SPS | 4800 SPS |
3 dB Point (Hz) | 11.5 | 13.8 | 34.5 | 34.5 | 69 | 221 | 1104 |
50 Hz Common Rejection (dB) | 100 | 60 | 10 | 10 | 2 | .1 | n/a |
60 Hz Common Rejection (dB) | 100 2 | 100 | 10 | 10 | 2 | .1 | n/a |
50 Hz Normal Rejection (dB) | 74 | 50 | 5 | 5 | n/a | n/a | n/a |
60 Hz Normal Rejection (dB) | 74 2 | 97 | 5 | 5 | n/a | n/a | n/a |
Effective Resolution (Bits) | 18 | 18 | 17 | 17 | 16 | 16 | 15 |
Effective Resolution (Current) | 0.08uA | 0.08uA | 0.16uA | 0.16uA | 0.32uA | 0.32uA | 0.64uA |
Settling Time (ms) | 80 | 66.7 | 26.7 | 26.7 | 13.3 | 4.17 | 0.83 |
Minimum Sample Time 3 (RTS msec) | 328 | 275 | 115 | 115 | 61 | 25 | 11 |
1
These are approximate to the 3dB point and intended to be similar to the IF8H device.2
REJ60 bit set to one.3
RTS Times are slightly longer than IF8H values because of sync 4 filter.Provide Feedback