Ptxx view (5069-IB16F/IB6F-3W) parameters
    The 
Ptxx
 view includes these parameters:Parameter  | Description  | 
|---|---|
Off -> On filter time  | Defines how long an Off to On input transition must remain in the On state before the device considers the transition valid.  | 
On -> Off filter time  | Defines how long an On to Off input transition must remain in the Off state before the device considers the transition valid.  | 
Enable timestamp latching  | Determines whether timestamps are latched. 
  | 
Capture timestamp for Off -> On input transition  | Determines whether a timestamp is recorded for the Off -> On input transition.  | 
Capture timestamp for On -> Off input transition  | Determines whether a timestamp is recorded for the On -> Off input transition.  | 
Enable chatter detection  | Sets chatter detection. When enabled, chatter from a device connected to one of its inputs (for example, rapid transitions from a failed contact) is ignored. Chatter can cause the device to timestamp invalid input transitions. Typically, chattering signals cause inputs to transition falsely many times in a relatively short period of time.  | 
Chatter count  | Determines the number of acceptable input transitions that can occur in a given time period before considering the input to be chatter. Valid values from 2 to 127.  | 
Chatter time  | Determines the amount of time,from 1 to 10000 milliseconds, within which the number of input transitions are counted.  | 