Device-defined data types (5069-OF8)
    Device-defined data type names vary for each device depending on selections made when the device was created.
These tables list and describe device-defined data types for the 5069-OF8 devices.
These tables include information for: 
- input (as indicated by an "I")
 - output (as indicated by an "O")
 - configuration (as indicated by a "C")
 
Device-defined data type: AB:5000_AO8:I:0
Connection Type: Data and Listen Only
Member Name  | Type  | Style  | Valid Values  | 
|---|---|---|---|
RunMode  | BOOL  | Decimal  | 0 = Idle 1 = Run 
  | 
ConnectionFaulted  | BOOL  | Decimal  | 0 = A connection exists between the device and the controller. 1 = Not connected  | 
DiagnosticActive  | BOOL  | Decimal  | 0 = No diagnostics active 1 = One or more diagnostics are active or the prognostics threshold is reached  | 
DiagnosticSequenceCount  | BOOL  | Decimal  | 0 to 255 Increments each time a distinct diagnostic condition is detected, and each time a distinct diagnostic condition transitions from detected to not detected.  | 
Ch0x.Fault  | BOOL  | Decimal  | 0 = No fault exists 1 = Fault exists A fault is a roll-up of all of the diagnostic conditions that the device can detect and indicates bad data. If there is a detailed data type member that indicates a given detected condition, this fault member does not affect the DiagnosticActive or DiagnosticSequenceCount members. However, if there is no detailed data type for a given detected condition, this fault member triggers both the DiagnosticActive member and increments/decrements the Diagnostic Sequence Count.  | 
Ch0x.Uncertain  | BOOL  | Decimal  | 0 = Valid data 1 = Data validity uncertain. Device is operating outside its designed operating range, or data is under manual or override control.  | 
Ch0x.NoLoad  | BOOL  | Decimal  | 0 = No load condition does not exist 1 = No load condition exists, meaning a signal wire is disconnected from the channel or the RTB is removed from the device.  | 
Ch0x.ShortCircuit  | BOOL  | Decimal  | 0 = No short circuit or overcurrent condition exists 1 = Short circuit or overcurrent exists  | 
Ch0x.OverTemperature  | BOOL  | Decimal  | 0 = Device temperature is not over the operating limits 1 = Device temperature is over the operating limits  | 
Ch0x.FieldPowerOff  | BOOL  | Decimal  | 0 = Field power is present 1 = Field power is not present  | 
Ch0x.InHold  | BOOL  | Decimal  | 0 = Channel is not holding 1 = Channel is holding  | 
Ch0x.NotANumber  | BOOL  | Decimal  | 0 = Last channel data received was a number 1 = Output value received from the originator is NotANumber (the IEEE NAN value). The output channel will hold its last state  | 
Ch0x.Underrange  | BOOL  | Decimal  | 0 = The input signal at the channel is greater than the minimum detectable signal. 1 = The input signal at the channel is less than or equal to the minimum detectable signal.  | 
Ch0x.Overrange  | BOOL  | Decimal  | 0 = The input signal at the channel is less than the maximum detectable signal. 1 = The input signal at the channel is greater than or equal to the maximum detectable signal.  | 
Ch0x.LLimitAlarm  | BOOL  | Decimal  | 0 = Alarm is not triggered 1 = Alarm is triggered  | 
Ch0x.HLimitAlarm  | BOOL  | Decimal  | 0 = Alarm is not triggered 1 = Alarm is triggered  | 
Ch0x.RampAlarm  | BOOL  | Decimal  | 0 = Alarm is not triggered 1 = Alarm is triggered  | 
Ch0x.CalFault  | BOOL  | Decimal  | 0 = Calibration did not fail 1 = A calibration session for a channel was interrupted or failed. CalFault is reset by product reset or power cycle.  | 
Ch0x.Calibrating  | BOOL  | Decimal  | 0 = Channel is not being calibrated 1 = Channel is being calibrated  | 
Ch0x.Data  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Ch0x.RollingTimestamp  | BOOL  | Decimal  | Any positive value.  RollingTimestamp is a continuously running timer that counts in milliseconds. When an input device scans its channels, it also records the RollingTimestamp value.  | 
Device-defined data type: AB:5000_AO8:O:0
Connection Type: Data
Member Name  | Type  | Style  | Valid Values  | 
|---|---|---|---|
Ch0x.LLAlarmEn  | BOOL  | Decimal  | 0 = Alarm is disabled 1 = Alarm is enabled  | 
Ch0x.LAlarmEn  | BOOL  | Decimal  | 0 = Alarm is disabled 1 = Alarm is enabled  | 
Ch0x.HAlarmEn  | BOOL  | Decimal  | 0 = Alarm is disabled 1 = Alarm is enabled  | 
Ch0x.HHAlarmEN  | BOOL  | Decimal  | 0 = Alarm is disabled 1 = Alarm is enabled  | 
Ch0x.RateAlarmEN  | BOOL  | Decimal  | 0 = Alarm is disabled 1 = Alarm is enabled  | 
Ch0x.LLimitAlarmUnlatch  | BOOL  | Decimal  | Transition from low to high unlatches alarm.  | 
Ch0x.HLimitAlarmUnlatch  | BOOL  | Decimal  | Transition from high to low unlatches alarm.  | 
Ch0x.RampAlarmUnlatch  | BOOL  | Decimal  | Transition from low to high unlatches alarm  | 
Ch0x.Data  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Device-defined data type: AB:5000_AO8:C:0
Connection Type: Data and Data with Calibration
Member Name  | Type  | Style  | Valid Values  | 
|---|---|---|---|
Ch0x.Range  | BOOL  | Decimal  | 0 = -10…10V 1 = 0…5V 2 = 0…10V 4 = 0…20 mA 5 = 4…20 mA  | 
Ch0x.AlarmDisable  | BOOL  | Decimal  | 0 = Alarms are enabled 1 = Alarms are disabled (default)  | 
Ch0x.LimitAlarmLatchEn  | BOOL  | Decimal  | 0 = Latching disabled (default) 1 = Latching enabled  | 
Ch0x.RampAlarmLatchEn  | BOOL  | Decimal  | 0 = Latching disabled (default) 1 = Latching enabled  | 
Ch0x.NoLoadEn  | BOOL  | Decimal  | 0 = Disabled (default) 1 = Enabled  | 
Ch0x.Disable  | BOOL  | Decimal  | 0 = Channel is enabled (default) 1 = Channel is disabled  | 
Ch0x.FaultMode  | BOOL  | Decimal  | 0 = Transition to user-defined value 1 = Hold Last State (default)  | 
Ch0x.ProgMode  | BOOL  | Decimal  | 0 = Transition to user-defined value 1 = Hold Last State (default)  | 
Ch0x.ProgramToFaultEn  | BOOL  | Decimal  | 0 = Channel remains in Program mode 1 = Channel transitions to Fault mode  | 
Ch0x.RampInRun  | BOOL  | Decimal  | 0 = Ramping disabled (default) 1 = Ramping enabled in Run mode  | 
Ch0x.RampToProg  | BOOL  | Decimal  | 0 = Ramping disabled (default) 1 = Ramping enabled to Program mode state  | 
Ch0x.RampToFault  | BOOL  | Decimal  | 0 = Ramping disabled (default) 1 = Ramping enabled to Fault mode state  | 
Ch0x.HoldForInt  | BOOL  | Decimal  | 0 = Unchecked 1 = Checked  | 
Ch0x.FaultValueStateDuration  | SINT  | Decimal  | 0 = Forever 1 = 1 second 2 = 2 seconds 5 = 5 seconds 10 seconds  | 
Ch0x.MaxRampRate  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Ch0x.LowSignal  | REAL  | Float  | -1.0E11 to 1.0E11 A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.  | 
Ch0x.HighSignal  | REAL  | Float  | -1.0E11 to 1.0E11 A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.  | 
Ch0x.LowEngineering  | REAL  | Float  | -1.0E11 to 1.0E11 A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.  | 
Ch0x.HighEngineering  | REAL  | Float  | -1.0E11 to 1.0E11 A combination of LowSignal, HighSignal, LowEngineering, and HighEngineering are used to scale the input data returned by the device.  | 
Ch0x.LowLimit  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Ch0x.HighLimit  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Ch0x.Offset  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Ch0x.FaultValue  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Ch0x.ProgValue  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Ch0x.FaultFinalState  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Device-defined data type: AB:5000_AO8_CAL:I:0 
Connection Type: Data with Calibration
Member Name  | Type  | Style  | Valid Values  | 
|---|---|---|---|
RunMode  | BOOL  | Decimal  | 0 = Idle 1 = Run  | 
ConnectionFaulted  | BOOL  | Decimal  | 0 = Good 1 = Bad  | 
DiagnosticActive  | BOOL  | Decimal  | 0 = No diagnostics active 1 = One or more diagnostics are active or the prognostics threshold is reached  | 
DiagnosticSequenceCount  | BOOL  | Decimal  | 0 to 255  | 
Ch0x.Fault  | BOOL  | Decimal  | 0 = Good 1 = Bad  | 
Ch0x.Uncertain  | BOOL  | Decimal  | 0 = Good 1 = Uncertain  | 
Ch0x.NoLoad  | BOOL  | Decimal  | 0 = No Load condition does not exist 1 = No load condition exists, meaning a signal wire is disconnected from the channel or the RTB is removed from the device.  | 
Ch0x.ShortCircuit  | BOOL  | Decimal  | 0 = No short circuit or overcurrent condition exists 1 = Short circuit or overcurrent exists  | 
Ch0x.OverTemperature  | BOOL  | Decimal  | 0 = Device temperature is not over the operating limits 1 = Device temperature is over the operating limits  | 
Ch0x.FieldPowerOff  | BOOL  | Decimal  | 0 = Field power is present 1 = Field power is not present  | 
Ch0x.InHold  | BOOL  | Decimal  | 0 = Channel is not holding 1 = Channel is holding  | 
Ch0x.NotANumber  | BOOL  | Decimal  | 0 = Last channel data received was a number 1 = Last channel data received was not a number  | 
Ch0x.Underrange  | BOOL  | Decimal  | 0 = Channel data is not beneath the underrange threshold 1 = Channel data is beneath  | 
Ch0x.Overrange  | BOOL  | Decimal  | 0 = Channel data is not above the overrange threshold 1 = Channel data is above the overrange threshold  | 
Ch0x.LLimitAlarm  | BOOL  | Decimal  | 0 = Alarm is not triggered 1 = Alarm is triggered  | 
Ch0x.HLimitAlarm  | BOOL  | Decimal  | 0 = Alarm is not triggered 1 = Alarm is triggered  | 
Ch0x.RampAlarm  | BOOL  | Decimal  | 0 = Alarm is not triggered 1 = Alarm is triggered  | 
Ch0x.CalFault  | BOOL  | Decimal  | 0 = Calibration did not fail 1 = Calibration failed  | 
Ch0x.Calibrating  | BOOL  | Decimal  | 0 = Channel is not being calibrated 1 = Channel is being calibrated  | 
Ch0x.CalGoodLowRef  | BOOL  | Decimal  | 0 = Valid Low Reference signal has not been sampled on this channel 1 = Valid Low Reference signal has been sampled on this channel  | 
Ch0x.CalBadLowRef  | BOOL  | Decimal  | 0 = Invalid Low Reference signal has not been sampled on this channel 1 = Invalid Low Reference signal has been sampled on this channel  | 
Ch0x.CalGoodHighRef  | BOOL  | Decimal  | 0 = Valid High Reference signal has not been sampled on this channel 1 = Valid High Reference signal has been sampled on this channel  | 
Ch0x.CalBadHighRef  | BOOL  | Decimal  | 0 = Invalid High Reference signal has not been sampled on this channel 1 = Invalid High Reference signal has been sampled on this channel  | 
Ch0x.CalSuccessful  | BOOL  | Decimal  | 0 = Calibration was not successful 1 = Calibration was successful and calibrating state has been exited.  | 
Ch0x.Data  | REAL  | Float  | -1.0E11 to 1.0E11  | 
Ch0x.RollingTimestamp  | BOOL  | Decimal  | Any value RollingTimestamp is a continuously running timer that counts in milliseconds. When an input device scans its channels, it also records the RollingTimestamp value.  | 
Device-defined data type: AB:5000_AO8_CAL:O:0
Connection Type: Data with Calibration
Member Name  | Type  | Style  | Valid Values  | 
|---|---|---|---|
Ch0x.LLimitAlarmUnlatch  | BOOL  | Decimal  | Transition from low to high unlatches alarm.  | 
Ch0x.HLimitAlarmUnlatch  | BOOL  | Decimal  | Transition from high to low unlatches alarm.  | 
Ch0x.RampAlarmUnlatch  | BOOL  | Decimal  | Transition from low to high unlatches alarm.  | 
Ch0x.Calibrate  | BOOL  | Decimal  | 0 = Calibration process is not started (default) 1 = Calibration process is started  | 
Ch0x.CalOutputLowRef  | BOOL  | Decimal  | 0 = Do not output Cal Low Reference 1 = Output Calibration Low Reference  | 
Ch0x.CalOutputHighRef  | BOOL  | Decimal  | 0 = Do not Output Cal High Reference 1 = Output Calibration High Reference Signal  | 
Ch0x.CalLowRefPassed  | BOOL  | Decimal  | 0 = Not sending Recorded Cal Low Ref 1 = Sending Recorded Cal Low Reference in Output Data for Calibration Verification  | 
Ch0x.CalHighRefPassed  | BOOL  | Decimal  | 0 = Not sending Cal High Reference 1 = Sending recorded Calibration High Reference Signal in Output Data for Calibration Verification  | 
Ch0x.CalFinished  | BOOL  | Decimal  | 0 = Channel not triggered to complete the calibration procedure 1 = Channel triggered to complete the calibration procedure  | 
Ch0x.Data  | REAL  | Float  | -1.0E11 to 1.0E11  | 