ControlLogix-XT 5590 Environmental Specifications

Environmental Specifications - ControlLogix-XT 5590 Controllers
Attribute
1756-L902TSXT, 1756-L905TSXT, 1756-L908TSXT, 1756-L915TSXT, 1756-L925TSXT, 1756-L950TSXT, 1756-L980TSXT, 1756-L9SPXT
Temperature, operating (SIL 2/PLd)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-25 °C ≤ Ta ≤ +70 °C
(-13°F ≤ Ta ≤ +158 °F)
Temperature, operating (SIL 3/PLe)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-25 °C ≤ Ta ≤ +70 °C
(-13°F ≤ Ta ≤ +158 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
-40…+85 °C
(-40…+185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
5…95% noncondensing
Conformal coated
Yes
Corrosive Atmosphere
  • ASTM B845-97 Method K Accelerated Test
(30-Day Exposure)
  • Plus additional Rockwell Automation proprietary accelerated corrosive environment test protocol for specific industries with sources of gaseous sulfur compounds.
Severity Level GX per ANSI/ISA 71.04-2013, Airborne Contaminants—Gases (up to 2100 angstroms of film growth per 30 days of copper and/or silver reactivity.)
Severity Level CX per IEC 60721-3-3:2019, Chemically Active Substances
Once the factory packaging seal is broken, plugs or covers must be installed in all unoccupied ports or slots for the product to maintain its corrosive atmosphere rating.
Vibration
IEC 60068-2-6 (Test Fc, Operating)
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions
IEC 61000-6-4
ControlLogix 5590 controllers require a NEMA 1 or equivalent, windowless, metal enclosure.
ESD immunity
IEC 61000-4-2
Radiated RF immunity
IEC 61000-4-3
EFT/B Immunity
IEC 61000-4-4
Shielded cable is recommended for a coarse Update Rate (CUR)/ Requested Packet Interval (RPI) of 6ms or less. To use unshielded cable, the CUR/RPI must be at least 8ms.
Surge Transient Immunity
IEC 61000-4-5
Conducted RF Immunity
IEC 61000-4-6