GuardLogix Safety Concept

The Safety Integrity Level (SIL) is the relative level of risk-reduction that is provided by a safety function.
The following table provides the SIL and Performance Level (PL) standards for the controllers:
  • The primary controller performs standard controller functionality and communicates with the safety partner to perform safety-related functions.
  • The safety partner works with the primary controller to perform safety-related functions in a SIL 3 system.
Safety Ratings for Safety Controllers
Controller System
IEC 61508
IEC 62061
IEC 61511
ISO 13849-1
Type-approved and certified for use in safety applications up to and including:
Suitable for use in safety applications up to and including:
Suitable for use in safety applications up to and including:
Suitable for use in safety applications up to and including:
GuardLogix®
5580 Controller Systems
Primary controller without a safety partner
SIL 2
SIL CL 2
SIL 2
Performance Level PLd (Cat. 3)
Primary controller with a safety partner
SIL 3
SIL CL 3
SIL 3
Performance Level PLe (Cat. 4)
Compact GuardLogix®
5380 Controller System with a Safety Partner
Cat. no. ends with a 2 (5069-L3xxxxxS2)
SIL 2
SIL CL 2
SIL 2
Performance Level PLd (Cat. 3)
Cat. no. ends with a 3 (5069-L3xxxxxS3)
SIL 3
SIL CL 3
SIL 3
Performance Level PLe (Cat. 4)
In documentation, safety ratings are expressed as follows:
  • SIL 2 represents SIL 2, SIL CL 2, and PLd
  • SIL 3 represents SIL 3, SIL CL 3, and PLe
TÜV Rheinland has approved
GuardLogix®
5580 and
Compact GuardLogix®
5380 controller systems for use in safety-related applications where the de-energized state is considered to be the safe state.
All I/O examples in this manual are based on achieving de-energization as the safe state for typical machine safety and emergency shutdown (ESD) systems.
IMPORTANT: As the system user, you are responsible for these items:
  • The setup, SIL rating, and validation of any sensors or actuators that are connected to the
    GuardLogix®
    system
  • Project management and functional test
  • Access control to the safety system, including password handling
  • Programming the application and the device configurations in accordance with the information in this safety reference manual and these publications:
    • ControlLogix 5580 and GuardLogix 5580 Controllers User Manual, publication 1756-UM543
    • CompactLogix 5380 and Compact GuardLogix 5380 User Manual, publication 5069-UM001
When applying functional safety, restrict access to qualified, authorized personnel who are trained and experienced.
Use programming software for
GuardLogix®
5580 and
Compact GuardLogix®
5380 controllers. Only the safety task, not standard tasks, can be used for safety functions.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal