Update Redundancy System Firmware
WARNING:
While you complete the process to update redundancy system firmware, there is a loss of redundancy. The controller runs the machinery without a backup until the update is complete.
You can update redundancy firmware to another revision while your process continues to run. Before you update your redundancy system to a new revision, consider the following:
- During the update procedures, you cannot use the Logix Designer application to change the mode of the controller. Instead, use the mode switch on the front of the controller.
- Remember the following when completing the tasks described in the rest of this section:
- Do not change the project other than with changes that are identified in these tasks.
- Verify that no one else is also changing the project.
- Do not use aFactoryTalk®Batch server to change equipment phase-states when upgrading your redundancy system.
To update your running redundancy system, complete this process.
- Prepare the redundant chassis for the firmware update.
- Update the redundancy module firmware in the secondary chassis.
- Update the redundancy module firmware in the primary chassis.
- Update other module firmware in the secondary chassis.
- Lock the system for update and initiate a locked switchover.
- Update other module firmware in the new secondary chassis.
- Synchronize the redundant chassis.
Provide Feedback