5034-IF4IH and 5034-IF4IHXT Analog 4 Input Isolated HART Modules

5034-IF4IH and 5034-IF4IHXT Wiring Diagram – Current Mode
5034-IF4IH and 5034-IF4IHXT Wiring Diagram – Voltage Mode
5034-IF4IH and 5034-IF4IHXT Functional Block Diagram
Technical Specifications - 5034-IF4IH, 5034-IF4IHXT
Attribute
5034-IF4IH, 5034-IF4IHXT
Input range, voltage
-10…+10V
0…10V
0…5V
Input range, current
0…20 mA
4…20 mA
4…20 mA - HART
Input impedance, voltage
≥ 1 MΩ
Input impedence, current, typical
without HART
155 Ω
Input impedence, current, typical
with HART
265 Ω
Module conversion method
Sigma-delta
16-bit ADC per channel
HART update rate
Typically 1 s
Additional device variables, configured commands, pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time.
Resolution, voltage
At 20 Hz notch filter
-10…+10V: 16 bits (366 µV/bit)
0…10V: 15 bits (366 µV/bit)
0…5V: 14 bits (732 µV/bit)
Resolution, current
At 20 Hz notch filter
0…20 mA: 15 bits (763 µA/bit)
4…20 mA: 15 bits (763 µA/bit)
Calibrated accuracy at 25 °C (77 °F),
HART disabled
Voltage: -10…+10V, ± 0.1% full scale with 20 Hz filter
Voltage: 0…10V, ± 0.1% full scale with 20 Hz filter
Voltage: 0…5V, ± 0.2% full scale with 20 Hz filter
Current: 0…20 mA, ± 0.1% full scale with 20 Hz filter
Current: 4…20 mA, ± 0.1% full scale with 20 Hz filter
Calibrated accuracy at 25 °C (77 °F),
HART enabled
Current: 4…20 mA, ± 0.1% full scale with 10 Hz filter
Current: 4…20 mA, ± 0.1% full scale with 20 Hz filter
Current: 4…20 mA, ± 0.3% full scale with 200 Hz filter
Current: 4…20 mA, ± 0.6% full scale with 1200 Hz filter
Calibrated accuracy over temperature range
-25…+60 °C (-13…+140 °F)
HART disabled
Voltage: -10…+10V, ± 0.2% full scale with 20 Hz filter
Voltage: 0…10V, ± 0.2% full scale with 20 Hz filter
Voltage: 0…5V, ± 0.4% full scale with 20 Hz filter
Current: 0…20 mA, ± 0.2% full scale with 20 Hz filter
Current: 4…20 mA, ± 0.2% full scale with 20 Hz filter
Calibrated accuracy over temperature range
-25…+60 °C (-13…+140 °F)
HART enabled
Current: 4…20 mA, ± 0.2% full scale with 10 Hz filter
Current: 4…20 mA, ± 0.2% full scale with 20 Hz filter
Current: 4…20 mA, ± 0.35% full scale with 200 Hz filter
Current: 4…20 mA, ± 0.65% full scale with 1200 Hz filter
Fastest scan time
1.0 ms with 9600 Hz notch filter
Fastest scan time, per module
1.0 ms
Input notch filter (Hz) selections
HART disabled: 10, 20 with 50/60 Hz noise rejection (Default), 200, 1200, 4800, 9600
HART enabled: 10, 20 with 50/60 Hz noise rejection (Default), 200, 1200
Input digital filter
First order lag, 0 ms (Default)
0…32,767 ms (32.767 s)
Input overvoltage protection, max
±32V DC
Overcurrent protection
Yes, 25 mA typical
Data value during overload condition
Full scale, overrange flag, data uncertain/data fault
Open circuit detection time
Voltage: 4 s typical
Current: 0.5 ms typical
Onboard data alarming
Yes
Scaling to engineering units
Yes
Real-time channel sampling
Yes
Data format
IEEE 754
32-bit floating point
Timestamp of inputs
Yes
CIP Sync
Yes
General Specifications - 5034-IF4IH, 5034-IF4IHXT
Attribute
5034-IF4IH, 5034-IF4IHXT
Number of inputs
4 channels, individually isolated
Supports current sourcing and differential signal
Configurable voltage or current mode at channel level
SA power voltage, nom
24V DC
SA power voltage range
10…30V DC (Derate to 3 channels for 10…18V DC)
SA power current, nom
125 mA
SA power current, max
300 mA
SA power current at no load
27 mA
Isolated sourcing voltage, min
(1)
20 V DC
Sourcing current limit per channel, max
25 mA, typical
SSV overcurrent detection
Yes
Power dissipation, max
1.60 W
Thermal dissipation, max
5.46 BTU/hr
Isolation voltage
250V (continuous), Basic Insulation Type, between system and SA power
250V (continuous), Basic Insulation Type, between SA power and input ports
250V (continuous), Basic Insulation Type, between individual input ports
250V (continuous), Basic Insulation Type, between system and input ports
Calibration
Factory-calibrated
Manual calibration supported
RIUP support
Yes
Electronic keying
Electronic keying via programming software
RTB key position (slot)
2, 6, 10
RTB supported
5034-RTB18, 5034-RTB18S
Wiring category
(2)
2 - Signal ports
2 - Power ports
Wiring specification
See Wiring Specifications for Removable Terminal Blocks in the PointMax I/O System Specifications Technical Data, publication 5034-TD001
Indicators
1 green/red module status indicator
1 green/red SA power status indicator
4 yellow/red I/O status indicators
Dimensions (HxWxD), approx
123.6 x 15.0 x 66.4 mm (4.87 x 0.59 x 2.61 in.)
Weight, approx
51.0 g (1.80 oz.) – 5034-IF4IH
53.0 g (1.87 oz.) – 5034-IF4IHXT
Enclosure type
None (Open-style)
North American temp code
T4
UKEX/ATEX temp code
T4
IECEx temp code
T4
(1) 20V DC is connected to screw via series impedance. Series impedance is as per value published. Measured voltage is Sourcing Voltage minus Voltage drop across series impedance based on the current drawn.
(2) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Use this Conductor Category information for planning conductor routing as described in the appropriate System Level Installation Manual.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.