Hold for Initialization
Hold for Initialization causes outputs to hold present state until the value commanded by
the controller matches the value at the output screw terminal within 0.1% of full scale,
providing a bumpless transfer.
If Hold for Initialization is selected, outputs hold if there is an occurrence of any of
these three conditions:
- Initial connection is established after power-up.
- A new connection is established after a communication fault occurs.
- There is a transition to Run mode from Program state.
- The module loses SA power. In this case, the data echo value goes to 0.0.
The
I.Chxx.InHold
tag for a channel indicates that the channel is holding.Provide Feedback