System Planning

Follow these rules when planning your system configuration:
  • The adapter is the leftmost component in the rack when in horizontal mounting.
  • Local PointMax I/O modules are installed to the right of the adapter.
  • The 5034-AENTR and 5034-AENTRXT adapters support a maximum of 16 I/O modules. You can expand the rack to 32 I/O modules with an expansion power (5034-EXP or 5034-EXPXT) between the two sets of 16 I/O modules.
  • Before powerup, verify that the end cap is installed on the last mounting base (MB) in the PointMax I/O system.
  • For vibration or shock environments, verify that DIN rail end anchors are installed at both ends of the system.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.