Safety Task Requirements
In Logix SIS applications, the safety task for
ControlLogix®
5590 controllers has the following requirements.Parameter | Requirement |
|---|---|
Period | Be sure that the safety task has enough time to execute its logic before it restarts:
|
Priority | A value of 1 is enforced to make the safety task the highest priority task. |
Watchdog | Enter a value of 5…500 ms. To avoid a fault that can shut down the safety task during a loss of redundancy, enter a value that is at least 5 ms higher than your safety task max scan time. For example, if your safety task max scan time is 5 ms, set your safety task watchdog to at least 10 ms. There is no fault to indicate that the safety task is consuming too much scan time. |
IMPORTANT:
When determining the safety task max scan time, we recommend that you perform several disqualifications and switchovers to get a more accurate time measurement that accounts for system dynamics.
Provide Feedback