2080-RTD2 plug-in module

2080-RTD2 is a 2-channel non-isolated Resistance Temperature Detector (RTD) input module that extends inputs for the controller. After adding a 2080-RTD2 plug-in module:
  • Five global variables are created in the controller project.
  • In
    Project Organizer
    , under
    Plug-in
    , a
    2080-RTD2
    node is created.
  • The 2080-RTD2 configuration page contains the following nodes. Select a node to view and configure the corresponding settings.
    • Overview
      : Displays the device image, catalog number, revision, product type, and slot number. Selecting
      Device definition
      opens the
      Device definition
      dialog to change the slot and revision, and to configure whether to fault the controller when the plug-in module is absent.
    • Variable
      : Lists the added variables with their variable names and data types.
    • Channel <x>
      : Configures the settings on channel
      <x>
      , where
      x
      represents channels from 0 through 1.
Channel x configurations
Setting
Description
RTD Type
Specifies the RTD input type for the channel.
Each RTD type value has a minimum and maximum temperature range.
Options are:
  • 100 PT 385
  • 200 PT 385
  • 500 PT 385
  • 1000 PT 385
  • 100 PT 392
  • 200 PT 392
  • 500 PT 392
  • 1000 PT 392
  • 10 CU 427
  • 120 Ni 672
  • 604 NiFe 518
The default setting is
100 PT 385
.
Data update rate
Specifies the channel update rate for data inputs.
Options are:
  • 470 Hz
  • 242 Hz
  • 123 Hz
  • 62 Hz
  • 50 Hz
  • 39 Hz
  • 33.2 Hz
  • 19.6 Hz
  • 16.7 Hz
  • 12.5 Hz
  • 10 Hz
  • 8.33 Hz
  • 6.25 Hz
  • 4.17 Hz
The default setting is
16.7 Hz
.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.