1756-RM3 Status Indicators

The 1756-RM3XT status indicators operate the same as 1756-RM3 status indicators.
1756-RM3 Status Display
Status Display
Item
Description
A
Alphanumeric display that scrolls messages approximately every 15 seconds.
B
Status indicators:
  • Link 1 and Link 2—Indicates the current state of Link 1 and Link 2.
  • NET—The network status indicator represents the status of the
    EtherNet/IP
    network.
  • MOD—The module status indicator represents the entire state of the redundancy module.
Status Messages
Message
Description
????
The initial state of the module is resolving. Wait for the resolution to finish. No action is required.
CPU Internal Thermal Fault
The module had to shut down after becoming too hot. This is a major nonrecoverable fault with fault code 0x2. To recover from the fault, reset the module.
Critical Temperature
The module is too hot or too cold. This is a major recoverable fault with fault code 0x5.
DISQ
The secondary redundancy module is disqualified. Check the type and revision of the secondary partner module.
Duplicate RM - Remove This RM
A duplicate redundancy module exists in the chassis. Remove the duplicate redundancy module.
Exxx
An error occurred during powerup. Following this error, the module resets and restarts. If the problem persists, provide the error message to Technical Support for further guidance.
Firmware Installation Required
The module is using boot firmware (revision 1.xxx) and requires a firmware update.
Flash in Progress
The module is updating its firmware. Wait for the firmware update to finish. No action is required.
Link X - 1 Gb/FULL
A supported SFP transceiver is detected in the specified channel (1 or 2), and the link is operating normally with no faults.
Link X - Disabled
The SFP transceiver in the specified channel (1 or 2) is disabled.
Link X - Down
No SFP transceiver is detected in the specified channel (1 or 2) and the transceiver has not been disabled. Possible causes include the following:
  • The cable is loose, disconnected, broken, or damaged
  • The signal is attenuated
  • The connector is loose
  • The partner redundancy module is powered down or in a major fault state
This is a minor recoverable fault. Once the link is detected, the redundancy module clears the fault.
LKNG
The secondary redundancy module is in the process of locking for update.
LOCK
The secondary redundancy module is locked for update.
Module Configuration Failure
Possible causes include the following:
  • The module configuration was not successfully stored to nonvolatile memory.
  • The redundancy module failed to apply fiber security configuration changes.
Module Configuration Load Failure
Possible causes include the following:
  • The module configuration was not successfully stored to nonvolatile memory.
  • The redundancy module failed to apply fiber security configuration changes.
Module Fault - Power Cycle or Reset Module
The module has a major nonrecoverable fault. Remove and reinsert the module. If module continues to display this message repeatedly after subsequent restarts, try the following:
  1. Disconnect the module from its partner.
  2. Remove all other modules from chassis.
  3. Restart the faulted module.
  4. If the module powers up correctly, reinsert modules into the chassis and update the redundancy module firmware.
Module Fault (AAA-BBB-CCC) - Power Cycle or Reset Module
The module has a major nonrecoverable fault. Save the displayed 9-character fault ID and then remove and reinsert module. For further investigation, provide the fault ID along with the fault log on the microSD™ card to Technical Support. If module continues to display this message repeatedly after subsequent restarts, try the following:
  1. Disconnect the module from its partner.
  2. Remove all other modules from chassis.
  3. Restart the faulted module.
  4. If the module powers up correctly, reinsert modules into the chassis and update the redundancy module firmware.
Module in Slot X Failed - Replace Module
The module in the specified slot (0…16) cannot reliably participate in the redundancy system because it not able to notify the redundancy module of failure. Remove and replace the module in the specified slot.
RM Failed – Replace Module
The redundancy module failed to pass the SysFail test. Remove and replace the redundancy module.
Not Compatible Partner Connected
The module is connected to a partner module with another major firmware revision or different major or minor software version.
Over Temperature
The module is hot, but not at a critical temperature. This is a minor recoverable fault with fault code 0x6.
PASS
Power-up tests successfully completed.
PRIM
The module is operating as the primary redundancy module. No action is required.
QFNG
The redundancy system is qualifying the secondary redundancy module. No action is required.
Rev XX.xxx
The major and minor firmware revision of the module.
RM Log Lost
Event logs were lost and the redundancy module is reinitializing the event log instances. The high availability of the module is not impacted, but the module may not be able to propagate events into the RMCT correctly. This message can appear after a redundancy module firmware update or redundancy module replacement. The message disappears in 180 seconds.
SD Card Failure
The microSD card has a fault. Possible causes include the following:
  • Power faults
  • Problems with partitions on the card
  • Card not mounting after a long wait
SD Card Format Invalid
The microSD card does not have a compatible FAT32 format.
SD Power Fault
The microSD card has a power fault.
SFP X - Missing
No SFP transceiver is detected in the specified channel (1 or 2). Possible causes include the following:
  • The transceiver is loosely connected
  • The transceiver is not installed
The message indicates a minor recoverable fault. The redundancy module clears the fault if the transceiver is detected or disabled.
SFP X - Unsupported
The SFP transceiver in the specified channel (1 or 2) is not supported by Rockwell Automation or the SFP standard is not recognized.
The message indicates a minor recoverable fault. Once the transceiver is removed or disabled, the redundancy module clears the fault.
SFP X - Faulted
The SFP transceiver in the specified channel (1 or 2) is faulted.
The message indicates a minor recoverable fault. Once the transceiver is removed or disabled, the redundancy module clears the fault.
SYNC
The redundancy system is synchronized with a qualified secondary redundancy module. No action is required.
TEST
The module is performing power-up tests
Link 1/Link 2 Status Indicator
Status
Description
Steady off
One of these conditions exists:
  • The module has a major recoverable or major nonrecoverable fault.
  • A non-volatile storage (NVS) update is in process.
  • The port is not connected.
  • The port is disabled.
  • No power is applied to the module.
Flashing green
The module is receiving traffic on the port.
Steady green
The port is active, but not receiving data.
Flashing red
One of these conditions exists:
  • Link 1 is connected to Link 2.
  • The port has an intermittent loss of communication.
Steady red
One of these conditions exists:
  • The port is enabled, but no SFP module is installed.
  • The SFP module is faulted or failed.
  • The SFP module is installed and operating, but has a mismatched vendor ID.
Flashing green, red, off
When green for approximately 250 ms, red for approximately 250 ms, and then off, the module is performing its power-up testing. The status indicator continues this sequence until the power-up testing is complete.
NET Status Indicator
Status
Description
Steady off
One of these conditions exists:
  • No power is applied to the module.
  • The module has a major nonrecoverable fault.
Flashing green
The module is ready to communicate with its partner but no connection has been made yet.
Steady green
The module is communicating with its partner.
Flashing green, red, off
When green for approximately 250 ms, red for approximately 250 ms, and then off, the module is performing its power-up testing. The status indicator continues this sequence until the power-up testing is complete.
MOD Status Indicator
Status
Description
Steady off
No power is applied to the module.
Flashing green
One of these conditions exists:
  • The module has not been configured.
  • A non-volatile storage (NVS) update is in process.
Steady green
The module is operating normally.
Flashing red
One of these conditions exists:
  • The module has a major recoverable fault.
  • A firmware update is required.
Steady red
The module has a major nonrecoverable fault.
Flashing green, red, green
When green for approximately 250 ms, red for approximately 250 ms, and then steady green, the module is performing its power-up testing. The status indicator continues this sequence until the power-up testing is complete.