Overload Protection
Overload Protection helps prevent damage to the output that can result when more current
is present at the output than it can handle.
An Overload or short circuit to ground condition can cause an increase in point
temperature and trigger a thermal shutoff to prevent damage to the output.
There is an Overload tag in the Diagnostic assembly.
Cause of Fault | Correction | Recover Time |
|---|---|---|
Overload condition | Remove the load from the output point. | After the Overload or short circuit to ground condition occurs,
the output point holds fault indications for 10 seconds until it
checks if the fieldfault is removed. |
Short circuit to ground condition | Correct the cause of the short circuit condition. |