100-E and 104-E Communication Interface Modules Specifications

For a complete list of standards compliance and certifications, visit our Product Certifications website, rok.auto/certifications, and use ‘1834-CT’ as your search term.

Technical Specifications

Power is provided to the devices via the 1486 flat media cable.
The data port on a 100/104-E-INT-X module enables data and communications to and from 140 ME Electronic Circuit Breakers or E100 (193-1EF) Advanced Overload Relays.
100-E and 104-E Communication Interface Module Technical Specifications
Attribute
Value
Network power (NP)
Input voltage
11V DC minimum, 26.4V DC maximum
Input current
30 mA maximum, continuous
Switched power (SP)
Input voltage
26.4V DC maximum
Input current
Variable based on 100-E contactor coil types
Auxiliary (aux) input
Current and voltage that is provided by 100-E/104-E via push-in 14...28 AWG to dry contact aux input as defined in IEC60947-1 standard
Data port connection
Via component serial interface cable 100-E-X-CBL

Input Current Specifications, Pick-up/Hold-in, for 100-E/104-E Coils

100-E and 104-E Communication Interface Module Input Current Specifications
Attribute
Value
Energy-efficient [EJ]
24…60V AC, 20…60V DC
100-E(09...38)EJ / 104-E(09...38)EJ
12…16 / 1.7 [W]
Standard AC/DC
24…60V AC, 20…60V DC
100-E(40...65)KJ / 104-E(40...65)KJ
25 / 2 [W]
100-E(80...96)KJ / 104-E(80...96)KJ
40 / 2 [W]
Low Consumption/Faster Drop-out DC
24V DC
100-E(09...38)QJ / 104-E(09...38)QJ
6 / 1.7 [W]
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.