Redundant Chassis Requirements
For a redundant chassis pair, you can use any ControlLogix® or ControlLogix-XT™ chassis of the same size. For example, if the primary chassis uses a 1756-A4 chassis, the secondary chassis must use a 1756-A4 chassis. Each redundant chassis in a pair must contain the components in the following table. If the chassis is used as a redundant gateway, then a controller is not required.
You can also use any number of optional slot filler modules, catalog number 1756-N2.
These configuration parameters must match for the components in a redundant chassis pair during normal system operation:
Required Component | Modules Allowed in Each Chassis |
|---|---|
Controller | 1, max |
Redundancy module | 1, max |
Communication module | 1, min 7, max |
IMPORTANT:
Do not place I/O modules in a redundant chassis.
- Module type
- Chassis size (all rack sizes are supported)
- Slot placement
- Firmware revision