Overcurrent Detection
The module includes built-in protection against overcurrent conditions caused by
mis-wiring. Common mis-wiring scenarios include:
- Sensor power (24V) V+n is shorted to RTNn at the terminal screws.During this state:
- SSVOverCurrentandSSVOverCurrentTimestampappear in Channel Diagnostics.
- Overrange Fault, Channel Fault, and Uncertain status displays in the input tag.
- The module is externally powered and input current causes an overrange condition.During this state:
- Overrange Fault, Channel Fault, and Uncertain status displays in the input tag.
When such conditions are detected, the module automatically limits current to protect
internal components.
NOTE:
The module uses internal current limiting to safeguard
hardware.