Device-defined data types (5094-OB32)

Device-defined data type names vary for each device depending on selections made when the device was created.
These tables include information for these data types:
  • input (as indicated by an "I")
  • output (as indicated by an "O")
  • configuration (as indicated by a "C")
Device-defined data type: AB:5000_DOn_Diag:I:0
Connection Type: Data and Listen Only Data
Member Name
Type
Style
Valid Values
RunMode
BOOL
Decimal
0 = Idle
1 = Run
ConnectionFaulted
BOOL
Decimal
0 = Good
1 = Bad
DiagnosticActive
BOOL
Decimal
0 = No diagnostics active
1 = One or more diagnostics are active or the prognostics threshold is reached
DiagnosticSequenceCount
SINT
Decimal
-128...127
The value of 0 is skipped except during device power-up.
Pt0x.Data
BOOL
Decimal
0 = Output is Off
1 = Output is On
Pt0x.Fault
BOOL
Decimal
0 = Good
1 = Bad
Pt0x.Uncertain
BOOL
Decimal
0 = Good
1 = Uncertain
Pt0x.NoLoad
BOOL
Decimal
0 = No Load condition does not exist
1 = No Load condition exists, meaning a signal wire is disconnected from the channel or the RTB is removed from the device
Pt0x.ShortCircuit
BOOL
Decimal
0 = No Short Circuit or Overcurrent condition exists
1 = Short Circuit or Overcurrent exists
Device-defined data type: AB:5000_DIn_Packed:I:0
Connection Type: Data and Listen Only Data
Member Name
Type
Style
Valid Values
RunMode
BOOL
Decimal
0 = Idle
1 = Run
ConnectionFaulted
BOOL
Decimal
0 = Good
1 = Bad
DiagnosticActive
BOOL
Decimal
0 = No diagnostics active
1 = One or more diagnostics are active or the prognostics threshold is reached
Uncertain
BOOL
Decimal
0 = Valid data
1 = Data validity uncertain. Device is operating outside its designed operating range, or data is under manual or override control.
DiagnosticSequenceCount
SINT
Decimal
-128...127
The value of 0 is skipped except during device power-up.
Pt0xData
BOOL
Decimal
0 = Output is Off
1 = Output is On
Pt0xFault
BOOL
Decimal
0 = Good
1 = Bad
Device-defined data type: AB:5000_DOn:O:0
Connection Type: Data
Member Name
Type
Style
Valid Values
Pt0x.Data
BOOL
Decimal
0 = Off
1 = On
Device-defined data type: AB:5000_DOn_Packed:O:0
Connection Type: Data
Member Name
Type
Style
Valid Values
Pt0xData
BOOL
Decimal
0 = Off
1 = On
Device-defined data type: AB:5000_DOn_Diag:C:0
Connection Type: Data
Member Name
Type
Style
Valid Values
Pt0x.FaultMode
BOOL
Decimal
0 = Transition to user-defined value
1 = Hold Last State (default)
Pt0x.FaultValue
BOOL
Decimal
0 = Output is Off
1 = Output is On
Pt0x.ProgMode
BOOL
Decimal
0 = Transition to user-defined value
1 = Hold Last State (default)
Pt0x.ProgValue
BOOL
Decimal
0 = Output is Off
1 = Output is On
Pt0x.FaultFinalState
BOOL
Decimal
0 = Output is Off
1 = Output is On
Pt0x.ProgramToFaultEn
BOOL
Decimal
0 = Channel remains in Program mode
1 = Channel transitions to Fault mode
Pt0x.NoLoadEn
BOOL
Decimal
0 = Disables no load detection
1 = Enables no load detection
Pt0x.FaultValueStateDuration
SINT
Decimal
0 = Forever
1 = 1 second
2 = 2 seconds
5 = 5 seconds
10 =10 seconds