Device-defined data types (5094-IA16)

Device-defined data type names vary for each device depending on selections made when the device was created.
These tables include information for these data types:
  • input (as indicated by an "I")
  • configuration (as indicated by a "C")
Device-defined data type: AB:5000_DIn:I:0
Connection Type: Data and Listen Only Data
Member Name
Type
Style
Valid Values
RunMode
BOOL
Decimal
0 = Idle
1 = Run
ConnectionFaulted
BOOL
Decimal
0 = Good
1 = Bad
DiagnosticActive
BOOL
Decimal
0 = No diagnostics active
1 = One or more diagnostics are active or the prognostics threshold is reached
DiagnosticSequenceCount
SINT
Decimal
-128...127
The value of 0 is skipped except during device power-up.
Pt0x.Data
BOOL
Decimal
0 = Output is Off
1 = Output is On
Pt0x.Fault
BOOL
Decimal
0 = Good
1 = Bad
Pt0x.Uncertain
BOOL
Decimal
0 = Good
1 = Uncertain
Device-defined data type: AB:5000_DIn_Diag:C:0
Connection Type: Data
Member Name
Type
Style
Valid Values
Pt0x.InputOffOnFilter
SINT
Decimal
1 ms (default)
Pt0x.InputOnOffFilter
SINT
Decimal
10 ms (default)
20 ms
Pt0x.FieldPowerDiagEn
BOOL
Decimal
0 = Field Power/SA Power Diagnostics is not sent to the controller.
1 = Field Power/SA Power Diagnostics is sent to the controller. Use this if the sensor uses the SA power in the terminal base.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.