Verify Qualification and Synchronization

After you identify the primary and secondary chassis and apply power to the redundant chassis pair, the redundancy modules run a series of checks and qualify the redundant chassis pair. The qualification process begins automatically.
While qualification occurs, the status message on the module display transitions from DISQ (disqualified) to QFNG (qualifying) to SYNC (synchronized). The process completes in 1…3 minutes.
To verify the qualification and synchronization status, refer to the status messages on the modules in the redundant chassis pair as described in the following tables.
Synchronized System
Primary Chassis Display
Secondary Chassis Display
Redundancy Module
Controller and Communication Module
Redundancy Module
Controller and Communication Module
PRIM
PwQS
SYNC
QS
Qualifying System
Primary Chassis Display
Secondary Chassis Display
Redundancy Module
Controller and Communication Module
Redundancy Module
Controller and Communication Module
PRIM and QFNG
PQgS
QFNG
QgS
System with a Primary and Disqualified Secondary
Primary Chassis Display
Secondary Chassis Display
Redundancy Module
Controller and Communication Module
Redundancy Module
Controller and Communication Module
PRIM
PwDS
DISQ
CMPT (modules compatible)
or
DSNP (no partner present)
In the
FactoryTalk® Linx
Redundancy Module Configuration Tool (RMCT), you can view the status of your system in the bottom-left corner of the dialog box.
Redundancy System Status in RMCT
Redundancy System Status in RMCT
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal