Environmental Specifications and Certifications

The following tables provide the environmental specifications and certifications for the PointMax expansion power.
Environmental Specifications - PointMax Expansion Power
Attribute
5034-EXP
5034-EXPXT
Temperature, operating
IEC 60068-2-1 (Test Ae, Operating Cold),
IEC 60068-2-2 (Test Be, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-25 °C ≤ Ta ≤ +60 °C (-13 °F ≤ Ta ≤ +140 °F) for horizontal orientation
-25 °C ≤ Ta ≤ +55 °C (-13 °F ≤ Ta ≤ +131 °F) for other orientations
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…+85 °C (-40…+185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Conformal coated
No
Yes
Corrosive Atmosphere
ASTM B845-97 Method K Accelerated Test (20-Day Exposure)
Severity Level G3
(1)
per ANSI/ISA 71.04–2013, Airborne Contaminants—Gases
Severity Level CX
(1) (2)
per IEC 60721-3-3:2019, Chemically Active Substances
Corrosive Atmosphere
  • ASTM B845-97 Method K Accelerated Test (30-Day Exposure)
  • Plus additional Rockwell Automation proprietary accelerated corrosive environment test protocol for specific industries with sources of gaseous sulfur compounds.
Severity Level GX
(3) (4)
per ANSI/ISA 71.04–2013, Airborne Contaminants—Gases
Severity Level CX
(4)
per IEC 60721-3-3:2019, Chemically Active Substances
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Repetitive shock, operating
IEC 60068-2-27:
25 g, 6 ms duration, 1000 shocks in each ± direction in each 3 axis
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
IEC 61000-6-4
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine wave 80% AM from 80…6000 MHz
EFT/B immunity
IEC 61000-4-4:
±3 kV @ 5 kHz on power ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine wave 80% AM from 150 kHz…80 MHz
Voltage dips and variations
IEC 61000-4-29:
10 ms interruption on MP ports
(1) The expansion power supply and the corresponding RTB must remain installed at all times, for the product to maintain its corrosive atmosphere rating.
(2) Up to 86.4 g/(m
2
.yr), mass loss of copper due to corrosion.
(3) Up to 2100 angstroms of film growth per 30 days of copper and/or silver reactivity.
(4) The expansion power supply and the corresponding RTB must remain installed at all times, once the factory packaging seal is broken, for the product to maintain its corrosive atmosphere rating.
Certifications - PointMax Expansion Power
Certification
(1)
5034-EXP, 5034-EXPXT
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470.
UK and CE
UK Statutory Instrument 2016 No. 1091 and European Union 2014/30/EU EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
UK Statutory Instrument 2016 No. 1101 and European Union 2014/35/EU LVD, compliant with:
EN 61010-2-201; Control Equipment Safety Requirements
UK Statutory Instrument 2012 No. 3032 and European Union 2011/65/EU RoHS, compliant with:
EN IEC 63000; Technical documentation
RCM
Australian Radiocommunications Act, compliant with:
EN 61000-6-4; Industrial Emissions
Ex
UK Statutory Instrument 2016 No. 1107 and European Union 2014/34/EU ATEX Directive, compliant with:
EN IEC 60079-0; General Requirements
EN IEC 60079-7; Explosive Atmospheres, Protection "e"
II 3 G Ex ec IIC T4 Gc
UL 24 ATEX 3272X and UL24UKEX2997X
IECEx
IECEx System, compliant with:
IEC 60079-0; General Requirements
IEC 60079-7; Explosive Atmospheres, Protection "e"
II 3 G Ex ec IIC T4 Gc
IECEx UL 24.0066X
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 4
Morocco
Arrêté ministériel n° 6404-15 du 1 er muharram 1437
Arrêté ministériel n° 6404-15 du 29 ramadan 1436