5034-OA4 and 5034-OA4XT Digital 4 AC Output Modules

5034-OA4 and 5034-OA4XT Wiring Diagram
5034-OA4 and 5034-OA4XT Functional Block Diagram
Technical Specifications - 5034-OA4, 5034-OA4XT
Attribute
5034-OA4, 5034-OA4XT
(1)
AC Mode
DC Mode
On-state voltage, min
85V AC
10V DC
On-state voltage, nom
120/240V AC
240V DC
On-state voltage, max
264V AC
250V DC
On-state voltage drop, max
1.5V AC @ 0.75 A
1.5V DC @ 0.75 A
Output current per point, min
5 mA
Output current per point, max
0.75 A
Output current per module, max
3 A
Off-state leakage current, max
(2)
1 mA
Surge current per point
5 A max for 25 ms, repeatable every 2 s
7 A max for 40 ms, repeatable every 8 s
5 A max for 25 ms, repeatable every 2 s
Output delay time (Backplane to screw)
Off-to-On
On-to-Off
1/2 cycle time (typ)
1.5 ms (typ)
Field (LA) power loss detection
Yes
No
Inductive load allowed per point, max
40 mH
No load detection diagnostics
Not supported
Output short circuit/overload/overtemperature detection
Output short circuit/overload protection
Pilot duty rating
Resistive/General/Pilot Duty
5 A inrush current, 0.75 A rated current @ 85…264V AC, 47…63 Hz
Resistive/General/Pilot Duty
5 A inrush current, 0.75 A rated current @ 10…250V DC
Output states in program mode per point
  • Hold Last State
  • On
  • Off (default)
Output states in communication fault mode per point
Duration of communication fault mode per point
  • 1 s
  • 2 s
  • 5 s
  • 10 s
  • Forever (default)
Output final state after communication fault mode per point
  • On
  • Off (default)
(1) The module does not support mixed AC and DC operation. All points operate in the same mode, either AC or DC, based on the module configuration.
(2) Recommended Loading Resistor - To limit the effects of leakage current through solid-state outputs, connect a loading resistor in parallel with the load during the Off-state. For example, use a 24 kΩ, 2 W resistor for 120V AC operation and a 48 kΩ, 5 W resistor for 240V AC operation.
General Specifications - 5034-OA4, 5034-OA4XT
Attribute
5034-OA4, 5034-OA4XT
(1)
AC Mode
DC Mode
Number of outputs
4 channels (1 group of 4), Sourcing
Voltage category
120/240V AC
Output voltage, nom
240V AC
240V DC
Output voltage range
85…264V AC
10…250V DC
LA Power voltage range
85…264V AC, 47…63 Hz
10…250V DC
LA Power current, max
3 A @ 120/240V AC, 50/60 Hz
3 A @ 250V DC
Power dissipation, max
(2)
1.31 W
Thermal dissipation, max
(2)
4.45 BTU/hr
Isolation voltage
250V (continuous), Reinforced Insulation Type, System to Field
No isolation between LA Power and Output ports
No isolation between individual Output ports
RIUP support
Yes
CIP Sync
Yes, slave only ordinary clock
Electronic keying
Electronic keying via programming software
RTB key positions (slot)
6, 13, 15
RTB supported
5034-RTB18, 5034-RTB18S
Wiring category
(3)
1 - Output ports
1 - Power ports
Wiring specification
See Wiring Specifications for Removable Terminal Blocks in the PointMax I/O System Specifications Technical Data, publication 5034-TD001
Indicators
1 green/red module status indicator
4 yellow/red I/O status indicators
1 green/red LA power status indicator
1 green/red module status indicator
4 yellow/red I/O status indicators
Dimensions (HxWxD), approx
123.6 x 15.0 x 66.4 mm (4.87 x 0.59 x 2.61 in.)
Weight, approx
44.0 g (1.55 oz) – 5034-OA4
48.0 g (1.69 oz) – 5034-OA4XT
Enclosure type
None (Open-style)
North American temp code
T4
UKEX/ATEX temp code
T4
IECEx temp code
T4
(1) The module does not support mixed AC and DC operation. All points operate in the same mode, either AC or DC, based on the module configuration.
(2) Value is measured at 60 °C (140 °F). Power dissipation varies with temperature.
(3) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Use this Conductor Category information for planning conductor routing as described in the appropriate System Level Installation Manual.