Overriding output state inhibits safety state of the point

WARNING:
Selection of "Hold" for
Output State During Program Mode and Communications Fault Mode
prevents the output point from going to the safe state, making the output point not suitable for a SIL or PL rated safety function.
Set
Output State During Program Mode and Communications Fault Mode
to "Off" to allow points to go to safe state
IMPORTANT:
TÜV Rheinland has approved GuardLogix 5580 and Compact GuardLogix 5380 controller systems for use in safety-related applications where the deenergized state is always considered to be the safe state. You must ensure configuration of each channel of the safety IO module is set for "Off" under the
Output State During Program Mode and Communications Fault Mode
selection to consider those output points as part of any equipment’s safety function.
Changing the setting of the
Output State during Program Mode and Communications Fault Mode
inhibits the safety state transition of the point when the settings change from
Off
to
Hold
Select
Apply
or
OK
to proceed with the change, select
No
to cancel the change, or select
Help
to view the Help.