Module-defined data types (5094-OW4IS)

These tables include information for the following:
  • input (as indicated by "I")
  • output (as indicated by "O")
Module-defined data type: AB:5000_SDO4:I:0
Member Name
Type
Style
Valid Values
RunMode
BOOL
Decimal
0 = Idle
1 = Run
ConnectionFaulted
BOOL
Decimal
0 = Connection is active
1 = No Connection
DiagnosticActive
BOOL
Decimal
0 = No diagnostics active
1 = One or more diagnostics are active or the prognostics threshold is reached
DiagnosticSequenceCount
SINT
Decimal
1 through 255
Pt00 through Pt03
AB:5000_SafetyReadback_Channel:I:0
Module-defined data type: AB:5000_SafetyReadback_Channel:I:0
Member Name
Type
Style
Valid Values
Ptxx.Readback
BOOL
Decimal
0 = Off
1 = On if 24V is on output terminal
Ptxx.Fault
BOOL
Decimal
0 = Good
1 = Bad
Ptxx.Uncertain
BOOL
Decimal
0 = Good
1 = Uncertain
Ptxx.ShortCircuit
BOOL
Decimal
0 = No short circuit or overcurrent condition detected
1 = Short circuit or overcurrent detected
Ptxx.FieldPowerOff
BOOL
Decimal
0 = Field power is present
1 = No field power is present
Ptxx.Status
BOOL
Decimal
0 = Fault
1 = Normal
Module-defined data type: AB:5000_SDO4:O:0
Member Name
Type
Style
Valid Values
Pt00 through Pt03
CHANNEL_SDO:O:0
Module-defined data type: CHANNEL_SDO:O:0
Member Name
Type
Style
Valid Values
Pt.xxData
BOOL
Decimal
0 = Output is Off
1 = Output is On
Pt.xxResetFault
BOOL
Decimal
0 = Manual fault reset is required to reset fault
1 = Auto reset, faults are cleared automatically when the fault condition goes away