Customer Supplied Control Bus Power—Frames 8...15

Customer connections to provide the control bus with 240V AC and 24V DC power are provided in the input bay and control bay of applicable
PowerFlex®
drive products.

240V AC Terminal Block and Control Bus Connections—Frames 8…15

Customer connections to provide the control bus with 240V AC and 24V DC power are provided in the input bay and control bay of applicable
PowerFlex®
drive products.
Use terminal block TB2 to connect an external 240V AC power source to
PowerFlex®
755TM bus supplies that do not have the internal C1 control transformer option.
IMPORTANT:
Do not connect an external 240V AC control power source to 755TM bus supplies that are equipped with the internal C1 control transformer option. See the system nameplate for 240V AC input requirements to verify that an external control power supply is required.
PowerFlex®
755TL and 755TR drive products come equipped with the C1 control transformer. An external control power supply is not required for these products.
An image depicting connections to a control bus connector
Terminal Block
Frame
Wire Size
Strip Length
Recommended Torque
IP21
IP54
TB2
8...11
8...9
6mm
2
(22...8 AWG)
12 mm (0.47 in.)
1.6 N•m (14.2 lb•in)
TB2
12
10
10mm
2
(18...6 AWG)
12 mm (0.47 in.)
2.3 N•m (20.4 lb•in)
TB2
11
16mm
2
(18...4 AWG)
16 mm (0.63 in.)
4 N•m (35 lb•in)
TB2
12
35mm
2
(12...1/0 AWG)
18 mm (0.70 in.)
5.8 N•m (51 lb•in)
Control bus
8...12
8...12
2mm
2
(26...14 AWG)
12 mm (0.47 in.)
— (spring type)

24V DC Terminal Block and Control Bus Connections—Frames 8…15

Use terminal block TB5 to connect an external 24V DC power source. This source provides auxiliary power to the control pod and other control circuits when main power has been removed.
An image depicting connections to a control bus connector
Terminal Block
Frame
Wire Size
Strip Length
Recommended Torque
IP20
IP54
TB5
8…12
8…12
6mm
2
(22...8 AWG)
12 mm (0.47 in.)
1.6 N•m (14.2 lb•in)
Control bus
8…12
8…12
6mm
2
(26...14 AWG)
12 mm (0.47 in.)
— (spring type
Product 24V DC Power Requirements
Product
Frame
Maximum Power Requirements (Watts)
755TL and 755TR drives
8
213
9
276
10
339
11
402
12
465
13
528
14
654
15
780
755TM bus supplies
8
182
9
213
10
245
11
276
12
308
13
339
14
402
15
465
755TM bus supplies with one 755TM common bus inverter
8
157
9
188
10
220
11
251
12
283
13
314
14
377
15
440
755TM bus supplies with two 755TM common bus inverters
8
313
9
376
10
439

TB2 and TB5 Terminal Block Locations—Frames 8...15

Control Bay TB2 Terminal Block Location
An image depicting the TB2 terminal block location in a control bay.
Frame 8 Input Bay TB2 and TB5 Terminal Block Locations
An image depicting the terminal block locations for a drive.
Frame 9 Input Bay TB2 and TB5 Terminal Block Locations
An image depicting the terminal block locations for a drive.
Frame 10, 11, 13, and 14 Input Bay TB2 and TB5 Terminal Block Locations
An image depicting the terminal block locations for a drive.
Frame 12 and 15, 400/480V, Input Bay TB2 and TB5 Terminal Block Locations
An image depicting the terminal block locations for a drive.
Frame 12 and 15, 600/690V, Input Bay TB2 and TB5 Terminal Block Locations
An image depicting the terminal block locations for a drive.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal