Replace a CIP Security-enabled 1756-EN4TR Module
WARNING:
Module replacement requires redeployment of the security policy.
To replace a
CIP Security™
-enabled 1756-EN4TR module, follow these steps.- If the security policy includesFactoryTalk® Linx, then removeFactoryTalk® Linxfrom the security policy and redeploy the security policy withoutFactoryTalk® Linx.
- Replace the 1756-EN4TR module in the disqualified chassis as described in Perform a Direct Module Replacement in the Secondary Chassis.
- Redeploy the security policy to the 1756-EN4TR module by using the Validate and Deploy option.
- If you removedFactoryTalk® Linxfrom the security policy in step 1, then addFactoryTalk® Linxback to the security policy and redeploy the security policy withFactoryTalk® Linx.The new 1756-EN4TR module becomes accessible inFactoryTalk® Linx.
- If the auto-synchronization setting in the Redundancy Module Configuration Tool (RMCT) is not set to Always, then on the Synchronization tab, select Synchronize Secondary.