Encoder Safety Configuration view parameters

The parameters on
Encoder Safety Configuration
define the safety connection. The update rate of the safety connection is typically slower than the standard connection.
Parameters
Parameter
Description
Monitor Input Voltage
This parameter for voltage input monitoring is always enabled.
Enable Position Scaling
Sets
Position Scaling
to 1 and enables the scaling function.
Enable Endless Shaft Functionality
Enables the endless shaft functionality.
Enable Endless Shaft Functionality
is disabled by default for multi-turn devices. For a single-turn device,
Enable Endless Shaft Functionality
is always disabled.
In a multi-turn device, this parameter is only enabled when
Enable Position Scaling
is selected.
Numerator
Sets the numerator for the endless shaft functionality, where the steps per revolution are set as a fraction. The valid values are from 1 through 4096. For a single-turn device, the value is hard-coded to 1. In a multi-turn device, the default value is 4096.
In a multi-turn device, this parameter is only enabled when
Enable Endless Shaft Functionality
is selected.
Denominator
Sets the denominator for the endless shaft functionality, where the steps per revolution are set as a fraction. The valid values are from 1 through 8192. For a single-turn device, the value is hard-coded to 1. In a multi-turn device, the default value is 1.
In a multi-turn device, this parameter is only enabled when
Enable Endless Shaft Functionality
is selected.
Resolution (CPR)
The valid values for
Resolution
are from 1 through 32768. When disabled, the value for
Resolution
is set to the default value of 32768. When
Enable Endless Shaft
is selected, the last value entered is displayed, but ignored.
This parameter is only enabled when
Enable Position Scaling
is selected and
Enable Endless Shaft Functionality
is not selected.
Revolutions
Sets the number of turns. In a multi-turn device, the valid values for
Revolutions
are 1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096. For a single-turn device, the
Revolutions
value is always disabled and hard-coded to 1. For a multi-turn device, the default value and the disabled value is 4096.
In a multi-turn device, this parameter is only enabled when
Enable Position Scaling
is selected and
Enable Endless Shaft Functionality
is not selected.
Range
When
Enable Position Scaling
is selected and
Enable Endless Shaft Functionality
is cleared, the value for
Range
is the
Resolution
value multiplied by the number of
Revolutions
. For a multi-turn device, the allowed values are from 4 through 134217728 and the default value is 134217728. For a single-turn device, the allowed values are 4 to 32768 and the default value is 32768.
This parameter is only enabled for multi-turn devices when
Enable Position Scaling
is selected and
Enable Endless Shaft Functionality
is selected.
Direction
Set the
Direction
of the count to
Clockwise
or
Counterclockwise
. The default value is
Clockwise
.
Velocity Units
The default value is Counts/s. The valid values are:
  • Counts/s: 1F04H
  • Counts/ms: 1F05H
  • Revs/s: 1F0EH
  • Revs/min: 1F0FH
  • Revs/h: 1F10H
Configuring the velocity units also configures the acceleration units:
  • Counts/s -> Counts/s
    2
  • Counts/ms -> Counts/ms
    2
  • Revs/s -> Revs/s
    2
  • Revs/min -> Revs/s
    2
  • Revs/h -> Revs/s
    2
Preset
Sets the
Preset
value, in counts. The maximum value is 1 less than the total measuring range. The valid values are 0 to (
Range
- 1).