Input Tag Definitions – 5034-OF4

Input Tags – 5034-OF4
Name
Data Type
Definition
Valid Values
RunMode
BOOL
Channel’s operating state
0 = Idle
1 = Run
When the value is 0, it means one of the following:
  • Connection is not up.
  • Connection has been opened but the module has not started producing data for the connection.
  • Because the controller is in Program Mode, the module is not applying the Output tag data but is applying the Program Mode state of the channels instead.
When the value is 1, it means the following:
  • Connection is up.
  • Module is producing data for the connection.
  • Output tag data is being applied.
ConnectionFaulted
BOOL
Indicates if a connection is running.
The module sets this tag to 0 when connected. If the module is not connected, it changes the tag to 1.
0 = A connection exists between the module and the controller
1 = Connection is timed out or inhibited.
DiagnosticActive
BOOL
Indicates if any diagnostics are active or if the prognostics threshold is reached.
0 = No diagnostics are active
1 = One or more diagnostics are active or the prognostics threshold is reached.
DiagnosticSequenceCount
SINT
Increments for each time a distinct diagnostic condition is detected, and when a distinct diagnostic condition transitions from detected to not detected.
-128…+127
The value of 0 is skipped except during module powerup.
Chxx.Fault
BOOL
Indicates that channel data is inaccurate and cannot be trusted for use in the application.
If the tag is set to 1, you must troubleshoot the module to correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes the tag to change to 1 is removed, the tag automatically resets to 0.
0 = No fault exists
1 = Fault exists
Chxx.Uncertain
BOOL
Indicates that the channel data can be inaccurate but the degree of inaccuracy is not known.
If the tag is set to 1, you must troubleshoot the module to correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes the tag to change to 1 is removed, the tag automatically resets to 0.
0 = Valid data
1 = Data validity uncertain
Chxx.NoLoad
BOOL
The signal wire is disconnected from the channel or the RTB is removed from the module.
This condition is detected only when the channel is used in current mode.
0 = No Load condition does not exist
1 = No Load condition exists
Chxx.ShortCircuit
BOOL
A Short Circuit or Overcurrent condition exists.
This condition is detected only when the channel is used in voltage mode.
0 = No Short Circuit or Overcurrent condition exists
1 = Short Circuit or Overcurrent condition exists
Chxx.OverTemperature
BOOL
Not applicable for this module
N/A
Chxx.FieldPowerOff
BOOL
Field power is not present at the channel.
0 = Field power is present
1 = Field power is not present
Chxx.InHold
BOOL
Indicates that the channel is currently holding until the received data value is within 0.1% range full scale of the current data value.
0 = Channel is not holding
1 = Channel is holding
Chxx.NotANumber
BOOL
Indicates that the last value received for the channel output data value was not a number.
0 = Last channel data received was a number
1 = Last channel data received was not a number
Chxx.Underrange
BOOL
Indicates that the commanded output data in output tag is below the Underrange threshold. When it happens, the actual output signal is limited at the threshold or the configured Low Limit (whichever is higher).
0 = Commanded output data is not below the underrange threshold
1 = Commanded output data is below the underrange threshold
Chxx.Overrange
BOOL
Indicates that the commanded output data in output tag is above the Overrange threshold. When it happens, the actual output signal is limited at the threshold or the configured High Limit (whichever is lower).
0 = Commanded output data is not above the overrange threshold
1 = Commanded output data is above the overrange threshold
Chxx.LLimitAlarm
BOOL
Triggered when the requested output value is below the configured Low Limit value. It remains set until the requested output is above the Low Limit.
If the Chxx.AlarmDisable tag is set to 1, that is, the output signal is still clamped at the Low Limit value. But the Low Limit alarm is not triggered.
0 = Alarm is not triggered
1 = Alarm is triggered
Chxx.HLimitAlarm
BOOL
Triggered when the requested output value is above the configured High Limit value. It remains set until the requested output is below the High Limit.
If the Chxx.AlarmDisable tag is set to 1, that is, the output signal is still clamped at the High Limit value. But the High Limit alarm is not triggered.
0 = Alarm is not triggered
1 = Alarm is triggered
Chxx.RampAlarm
BOOL
Indicates that the analog output has been commanded to change value in a way such that the Maximum Ramp Rate is exceeded.
0 = Alarm is not triggered
1 = Alarm is triggered
Chxx.CalFault
BOOL
Indicates the last attempted Calibration for this channel failed.
This tag is cleared, that is, set to 0, when power is cycled to the module or a successful calibration for the range on the channel is performed.
0 = Calibration did not fail
1 = Calibration failed
Chxx.Calibrating
BOOL
Indicates the channel is currently being calibrated.
0 = Channel is not being calibrated
1 = Channel is being calibrated
Chxx.CalGoodLowRef
BOOL
Indicates that a valid Low Reference measurement was passed through the output tag to the module.
IMPORTANT: This tag is available only when you use the Data with Calibration connection type in the Device Definition. If you use the Data connection type, this tag does not appear in the module tags.
0 = Valid Low Reference signal has not been sampled on this channel
1 = Valid Low Reference signal has been sampled on this channel
Chxx.CalBadLowRef
BOOL
Indicates that an invalid Low Reference signal has been sampled on this channel.You must correct this condition to successfully calibrate the module.
If calibration is aborted with an invalid Low Reference signal, the Chxx.CalFault tag is set for this channel until a successful calibration is performed.
IMPORTANT: This tag is available only when you use the Data with Calibration connection type in the Device Definition. If you use the Data connection type, this tag does not appear in the module tags.
0 = Invalid Low Reference signal has not been sampled on this channel
1 = Invalid Low Reference signal has been sampled on this channel
Chxx.CalGoodHighRef
BOOL
Indicates that a valid High Reference measurement was passed through the output tag to the module.
IMPORTANT: This tag is available only when you use the Data with Calibration connection type in the Device Definition. If you use the Data connection type, this tag does not appear in the module tags.
0 = Valid High Reference signal has not been sampled on this channel
1 = Valid High Reference signal has been sampled on this channel
Chxx.CalBadHighRef
BOOL
Indicates that an invalid High Reference signal has been sampled on this channel.
You must correct this condition to successfully calibrate the module.
If calibration is aborted with an invalid High Reference signal, the Chxx.CalFault tag is set for this channel until a successful calibration is performed.
IMPORTANT: This tag is available only when you use the Data with Calibration connection type in the Device Definition. If you use the Data connection type, this tag does not appear in the module tags.
0 = Invalid High Reference signal has not been sampled on this channel
1 = Invalid High Reference signal has been sampled on this channel
Chxx.CalSuccessful
BOOL
Indicates calibration on this channel is complete and the Calibrating state has been exited.
This tag remains set after valid calibration as long as connection is open.
IMPORTANT: This tag is available only when you use the Data with Calibration connection type in the Device Definition. If you use the Data connection type, this tag does not appear in the module tags.
0 = Calibration was not successful
1 = One of the following:
  • Calibration was successful and calibrating state has been exited.
  • Calibration data is present and applied.
Chxx.Data
REAL
Indicates the signal value currently output at the RTB in scaled Engineering Units.
Any value
Chxx.RollingTimestamp
INT
Continuously-running 15-bit timer that counts in milliseconds.
Whenever the data echo value changes, the output module updates the value of the RollingTimestamp.
0…32,767
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal