Points view parameters (1732E-IB16M12SOEDR)

Use this view to configure Off → On, On → Off parameters, timestamping, and Open Wire Detection for the input channels on the device.
Inputs
Parameter
Description
Off → On Filter Time
Specifies the Off to On filter time in milliseconds to delay transitions from Off to On. This is useful for filtering out transients in noisy environments.
Valid values are:
  • 0 ms
  • 1 ms
    (default)
  • 2 ms
  • 4 ms
  • 8 ms
  • 16 ms
This parameter is not available in Run mode.
On → Off Filter Time
Specifies the On to Off filter time in milliseconds to delay transitions from On to Off. This is useful for filtering out transients in noisy environments.
Valid values are:
  • 0 ms
  • 1 ms
    (default)
  • 2 ms
  • 4 ms
  • 8 ms
  • 16 ms
This parameter is not available in Run mode.
Points
Indicates the points to which the configuration applies.
Open Wire Detection
Enables or disables Open Wire Detection by selecting or clearing the checkbox.
This parameter is not available in Run mode.
Fault Status
Displays the input channel’s current Fault status.
Timestamping
Parameter
Description
Latch Timestamps
Enables or disables Latch Timestamps option for input channels.
Off → On
On → Off
Enables or disables Timestamp Off to On or On to Off for all input channels.
Other Configuration
Parameter
Description
Refresh
Refreshes the
Fault Status
values in this view.
This option is available while online.
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.