Temperature

Damping

The damping makes it possible to damp the fluctuations of the measured values of the temperature:
  • on the FLOWave display,
  • on the PLC inputs.
The damping of the temperature comes in addition to the damping set for each analog output.
The damping is not applied to the new measured value if the 2 following conditions are met:
  • a Low, Medium or High damping level is active,
  • and the variation between 2 values that are measured one after the other is higher than 20 °C.
The refresh time has no effect on the damping of the measured values.
By default, the measured temperature values are not damped.
Temperature damping level selections
Damping level
Response time
None
0 s
Low
1 s
Medium
10 s
High
30 s