Differentiation Factor
The differentiation factor (DF) is a dimensionless measurement value which can be used to
identify the liquid flowing through the pipe.
Before SW version A.05.00.00, differentiation factor was named density factor. Given the fact
that the option density appeared, the name was changed in order to avoid confusion.
The DF is a non-calibrated acoustic measurement based on the measurement of the speed of
sound in the liquid and can be compensated by temperature. The DF gives an idea of the density
of most of aqueous liquids. By default, the temperature compensation is related to water.
Air bubbles in the liquid have an unwanted effect on the DF accuracy.
The device measures DFs in the range of 0.8...1.3.
- If a liquid flowing through the pipe has a higher density than water, the measured DF is higher than 1.
- If a liquid flowing through the pipe has a lower density than water, the measured DF is lower than 1.
- The DF of water is in the range of 0.95...1.05.
- The DF of tomato ketchup is in the range of 1.1...1.3.
a0 + a1T + a2T
2
+ a3T3
+ a4T4
+ a5T5
Damping
The damping makes it possible to damp the fluctuations of the measured values of the
differentiation factor (DF):
- on the display,
- on the totalizers,
- on the PLC input.
The damping is not applied to the new measured value if the 2 following conditions are met:
- a Low, Medium or High damping level is active,
- and the variation between 2 values that are measured one after the other is higher than 30 % (for example when changing the liquid in the pipe).
The Low damping level or no damping at all (None) are suited for applications/processes
that need fast response times.
The Medium damping level or the High damping level are suited if the DF values change
slowly.
Damping level | Response time |
|---|---|
None | 0 s |
Low | 1 s |
Medium | 10 s |
High | 30 s |