Missing Pulse Detection
Missing Pulse Detection alerts you when a new pulse is not available to count within a
configurable time period. When a missing pulse is detected, the Missing Pulse Alarm is
triggered.
To use Missing Pulse Detection, you must complete the following steps:
- Configure the Missing Pulse Alarm Limit to establish the maximum length of time between pulses before which the Missing Pulse Alarm is triggered.Go to Module Properties → Counterxx → Alarm to set the Missing Pulse Alarm Limit.
- Set theO.Counterxx.MissingPulseAlarmEntag to 1.If this tag is not set to 1, the alarm is not enabled and you are not alerted when a missing pulse occurs.
When the Missing Pulse Alarm is triggered, the
I.Counterxx.MissingPulseAlarm
tag
goes to 1.Missing Pulse Detection is commonly used in high frequency applications. A missing pulse
typically indicates the loss of a counting device, for example, an encoder. The loss of
a counting device often has a significant impact on the application conditions and
immediate system action is used to account for the impact.