PointMax I/O in a Logix 5000 Control System
Logix 5000 controllers use PointMax standard and safety I/O modules to control devices in
a control system. The controllers access the modules over an EtherNet/IP network. The
PointMax I/O modules use mounting bases (MB) and removable terminal blocks (RTB) to
connect field-side wiring.
I/O modules use the Producer/Consumer network communication model. This communication is
an intelligent data exchange between modules and other system devices in which each
module produces data without first being polled.
Use PointMax I/O modules as remote I/O modules that are accessible via an EtherNet/IP
network. The modules are installed to the right of a PointMax EtherNet/IP adapter (when
mounted in an upright horizontal orientation).
Logix 5000 controllers can exchange the data with the modules over an EtherNet/IP
network. The below figure shows a Compact GuardLogix® 5380 safety controller with a
PointMax EtherNet/IP adapter, and both standard and safety I/O modules. Safety
controllers support both standard and safety PointMax I/O modules.
PointMax Standard and Safety I/O Modules in a Logix 5000 Control System
Provide Feedback