5034-STEPD and 5034-STEPDXT Dual Stepper Drive Module

5034-STEPD and 5034-STEPDXT Wiring Diagram
5034-STEPD and 5034-STEPDXT Functional Block Diagram
Technical Specifications - 5034-STEPD, 5034-STEPDXT – Stepper Motor Drive Module
Attribute
5034-STEPD, 5034-STEPDXT
Motor type
2-phase bipolar stepper motor (4-wire, 6-wire, or 8-wire)
Number of motors, max
2
Motor input voltage
Follow SA supply
Motor microsteps
1, 2, 4, 8, 16, 32, 64, 128 (Default), 256
Motor phase current, max (continuous)
1 motor connected
2.0 A, rms @ 40 °C (104 °F)
1.75 A, rms @ 60 °C (140 °F)
Motor phase current, max (continuous)
2 motors connected
1.5 A, rms @ 40 °C (104 °F)
1.25 A, rms @ 60 °C (140 °F)
Motor peak current
Applicable for single motor
4.0 A rms for 5 s max followed by 20% of peak current as hold current, repeatable every 60 s
Motor speed, max
2400 RPM
Move commands supported
Position (Absolute and Relative), Velocity, Jog
Short to SA detection
Yes
Short circuit detection
Yes
Motor coil short detection
Yes
Over temperature detection
Yes
Technical Specifications - 5034-STEPD, 5034-STEPDXT – Digital Input
Attribute
5034-STEPD, 5034-STEPDXT
On-state voltage range
10…30V DC
On-state current, min
2 mA
On-state current, nom
2.35 mA
On-state current, max
2.8 mA
Off-state voltage, max
5V DC
Off-state current, max
1.5 mA
Input impedance, min
3.5 kΩ @ 10V DC
Input impedance, nom
10.21 kΩ @ 24V DC
Input impedance, max
15 kΩ @ 30V DC
Input delay time (screw to backplane), max
Off-to-On
On-to-Off
150 µs
Input filter time
Off-to-On
On-to-Off
0 µs, 100 µs, 200 µs, 500 µs, 1 ms (Default), 2 ms, 5 ms, 10 ms, 20 ms, 50 ms
Technical Specifications - 5034-STEPD, 5034-STEPDXT – MTO
Attribute
5034-STEPD, 5034-STEPDXT
On-state voltage range
18…30V DC
On-state current, min
2 mA
On-state current, nom
2.35 mA
On-state current, max
8 mA
Off-state voltage, max
5V DC
Off-state current, max
1 mA
Input impedance, min
2.25 kΩ @ 18V DC
Input impedance, nom
10.21 kΩ @ 24V DC
Input impedance, max
15 kΩ @ 30V DC
MTO to motor drive off delay, typical
10 ms
General Specifications - 5034-STEPD, 5034-STEPDXT
Attribute
5034-STEPD, 5034-STEPDXT
Number of motors
2
MTO
1 channel, isolated
Number of inputs
2 channels, sinking
SA power voltage, nom
24V DC
SA power voltage range
18…30V DC
SA power current, nom
5 A
SA power current, max
5.1 A
SA power current at no load
12 mA
SA reverse polarity protection
Yes
Power dissipation, max
(1)
1.55 W
Thermal dissipation, max
(1)
5.29 BTU/hr
Isolation voltage
250V (continuous), Basic Insulation Type, System to Field
250V (continuous), Basic Insulation Type, MTO to Field, MTO to System
No isolation between SA power and inputs
No isolation between individual inputs
RIUP support
Yes
CIP Sync
Slave only ordinary clock
Electronic keying
Electronic keying via programming software
RTB key positions (slot)
3, 7, 11
RTB supported
5034-RTB18, 5034-RTB18S
Wiring category
(2)
2 - Signal ports
2 - Power ports
Wiring specification
See Wiring Specifications for Removable Terminal Blocks in the PointMax I/O System Specifications Technical Data, publication 5034-TD001
Indicators
1 green/red module status indicator
1 green/red SA power status indicator
2 yellow/red Axis Motor status indicators
2 yellow input status indicators
1 yellow/red MTO status indicator
Dimensions (HxWxD), approx
123.6 x 15.0 x 66.4 mm (4.87 x 0.59 x 2.61 in.)
Weight, approx
46.0 g (1.62 oz.) – 5034-STEPD
49.0 g (1.73 oz.) – 5034-STEPDXT
Enclosure type
None (Open-style)
North American temp code
T4
UKEX/ATEX temp code
T4
IECEx temp code
T4
(1) Value is measured at 60 °C (140 °F). Power dissipation varies with temperature.
(2) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. Use this Conductor Category information for planning conductor routing as described in the appropriate System Level Installation Manual.
Wiring Specification – Motor Axis
Wire Type
Wire Range
Stranded and solid copper, shielded
0.34…1.5 mm
2
(22…16 AWG)
Screw RTB tightening torque: 0.22…0.25 N•m (1.95…2.21 lb•in)
Recommended strip length: 10 mm ± 0.4 mm (0.39 in. ± 0.016 in.)
The maximum cable length for motor drive output to the motor is 10 m (33 ft).
For motor current of 1 A or greater, we recommend using a 1.5 mm
2
(16 AWG) cable.
Wiring Specification – MTO
Wire Type
Wire Range
Stranded and solid copper
0.34…1.5 mm
2
(22…16 AWG)
Screw RTB tightening torque: 0.22…0.25 N•m (1.95…2.21 lb•in)
Recommended strip length: 10 mm ± 0.4 mm (0.39 in. ± 0.016 in.)
Route the MTO+/MTO− cables separately from all other wiring, particularly power and motor cables. Maintain physical separation in accordance with the wiring category guidance in the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Connect Multiple MTOs to the Same MTO Power Supply
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal