I/O Modules Status Indicators

PointMax I/O modules include status indicators such as SA power, LA power, module status, and I/O channel status to indicate module operating conditions and behavior. Not all I/O modules include an SA power status indicator. Some modules, such as AC I/O modules, include an LA power status indicator. For more information about these indicators, see PointMax I/O System Specifications Technical Data, publication 5034-TD001.
For detailed, module-specific status indicator information, see the module user manual listed in the Additional Resources.

SA Power Status Indicator

Interpret SA Power Status Indicator
Indicator State
Description
Steady red
One of the following:
  • There is no SA power to the module or SA power is not in the valid range.
  • A safety connection cannot be made or maintained (safety modules only).
Steady green
The SA power is in the valid range.

LA Power Status Indicator

Interpret LA Power Status Indicator – 5034-OA4 and 5034-OA4XT
Indicator State
Description
Steady red
There is no LA power to the module or LA power is not in the valid range.
Steady green
The LA power is in the valid range.

Module Status Indicators

Interpret Module Status Indicators
Indicator State
Description
Off
The module is not powered.
Steady red
The module experienced a nonrecoverable fault.
Flashing red and green
The device is in a self-test mode.
Flashing red
One of the following conditions exists:
  • A module firmware update is in progress.
  • A module firmware update attempt failed.
  • The device has experienced a recoverable fault.
  • A connection to the module has timed out.
Flashing green
The module has no I/O connections.
Steady green
The module is operational and all I/O connections are active.

I/O Channel Status Indicators

Interpret I/O Channel Status Indicators – Standard I/O Modules
Indicator State
Description
Off
One of the following:
  • The channel is Off.
  • There is no backplane power.
Steady yellow
One of the following:
  • The channel is On.
  • The channel is operating normally.
Flashing red
A fault condition is detected. Examples include field power loss, a short circuit condition, an open wire, or an overrange condition.
Interpret I/O Channel Status Indicators – Safety Digital I/O Modules
Indicator State
Description
Off
One of the following:
  • The point is Off.
  • The point is not used.
  • There is no backplane power.
Steady yellow
The point is operating normally.
Flashing red
The module experienced one or more recoverable faults.
Steady red
One of the following:
  • A Field Power Loss condition exists.
  • An internal channel fault exists.