Sequence Detail Control command controls

Use these commands to control an
Equipment Sequence
using the Sequence Detail Control. The availability of some commands depends on the selected
Equipment Sequence
owner, state, mode, and failure status. Select
More
to display all the commands on the toolbar.
These commands are always displayed:
  • Take/Release ownership
  • Set ID
  • Start
  • Hold
  • Restart
  • Stop
  • Abort
  • Reset
  • More/Less
These commands are available after selecting the
More
button and can be hidden by selecting the
Less
button:
  • Initialize parameters
  • Clear Failures
  • Pause/Cancel Pause
  • Auto Pause/Cancel Auto Pause
  • Resume
  • Enter/Exit Manual
  • Step change
  • Force transition
Icon
Command
Description
L5K_SILC_unselected_takeownership
Take Ownership
Take ownership of the
Equipment Sequence
. Taking ownership means that this application now has the right to command this
Equipment Sequence
; other internal sequencers, external sequencers, and operators are not allowed to command this sequence.
L5K_SILC_takeownership_sequence_V25
Release Ownership
Release ownership of the
Equipment Sequence
. Releasing ownership means that internal sequencers, external sequencers, and operators with attachments are allowed to command this sequence.
L5K_SILC_EquipSeqCommand_SetIDbutton
Set ID
Opens the
Set Sequence ID
dialog box where you can assign an identifier of up to 82 characters to the
Equipment Sequence
. This command is enabled only when an
Equipment Sequence
is idle.
Initialize Parameters
Reinitialize all sequencing parameter and step tag value fields with their configured Initial Value.
Step Change
Make the next step of the
Equipment Sequence
active and able to be commanded.
L5K_SILC_StartIcon_v26
Start
Start execution of the
Equipment Sequence
.
L5K_SILC_HoldIcon_v26
Hold
Halt all connected phases for the
Equipment Sequence
and stop evaluating transitions until the
Equipment Phase
runs its Hold routine.
L5K_SILC_RestartIcon_v26
Restart
Resume execution of the
Equipment Sequence
from the HELD state.
L5K_SILC_StopIcon_v26
Stop
Stop all connected phases and active transitions for the
Equipment Sequence
.
L5K_SILC_AbortIcon_v26
Abort
Abort all connected phases and active transitions for the
Equipment Sequence
.
L5K_SILC_ResetIcon_v26
Reset
Reset any remaining active phases for the
Equipment Sequence
.
Clear Failures
Clear the failure flags on the
Equipment Sequence
.
L5K_SILC_pause_icon_V25
Pause
Pause execution of the
Equipment Sequence
. When the active transition evaluates TRUE, it does not transition to the FIRING state until you select
Resume
. When paused, select to cancel pause.
L5K_SILC_autopause_icon_V25
Auto-Pause
Automatically pause the
Equipment Sequence
as transitions evaluate TRUE. When you select
Resume
, the next transitions fires, but the
Equipment Sequence
pauses again after each transition evaluates TRUE. When auto-pause is enabled, select to cancel auto-pause.
L5K_SILC_ResumeIcon_v26
Resume
Continue execution of the
Equipment Sequence
when the substate is Paused..
L5K_SILC_AutomaticModeIcon_v26
Enter Manual
Put the
Equipment Sequence
in
Manual
mode, in which the sequencing engine does not automatically fire transitions, and an operator commands the
Equipment Sequence
step by step. On the toolbar, only the
Release Ownership
,
Pause
,
Auto-Pause
, and
Automatic
commands are enabled.
L5K_SILC_ManualModeIcon_v26
Exit Manual
Put the
Equipment Sequence
in
Automatic
mode, which allows the sequencing engine to automatically fire transitions and execute the
Equipment Sequence
.