Configure the 1770-KFD driver

  1. From the
    Port Select
    list, select the communication port on the computer, to which your 1770-KFD driver is attached (COM1, COM2, COM3, or COM4).
  2. From the
    Data Rate
    list, select the rate of data transfer for the selected Serial Port (9600, 19200, 38400, or 57600).
  3. Enter the
    Node Address
    (MAC ID) that the 1770-KFD driver uses on the DeviceNet network. You can enter a value from 0 through 63 for the MAC ID.
  4. Select the
    Data Rate,
    at which your DeviceNet network is operating (125K, 250K, or 500K).
  5. If you want to use the Modem Dialer, select the Use Modem Dialer check box, and click
    Configure Dialer
    to open the Dialer Configuration window.