SLC 500 enhanced: timer, counter, and control files: analog member addressing optional syntax

This addressing syntax applies to SLC 5/03 OS301 and SLC 5/04.
Fnnn:eee.o/bb
F
(file type)
T
Timer
C
Counter
R
Control
nnn
(optional file number)
Timer
4, 9-255 decimal
Counter
5, 9-255 decimal
Control
6, 9-255 decimal
Timer, counter and control file types use the default file number if the file number is absent. The default numbers are 4 (timer), 5 (counter), and 6 (control).
eee
(element number)
0-255 decimal
o
(word offset)
1-2 decimal
bb
(optional bit number)
0-15 decimal
Example
R44:72.1/14