AckPage method (AlarmSummary object)

Acknowledges the page of alarms currently visible in the event list.
Syntax
object
.
AckPage
([
ShowDialog
as
Boolean
], [
Comment
as
String
])
where
object
—
the name of an AlarmEventSummary object.
ShowDialog
—
optional parameter that controls whether the
Comment
dialog box is displayed before the alarms are acknowledged.
  • TRUE.
    The default value is TRUE. If ShowDialog = TRUE, then the
    Acknowledge Alarm with Comment
    dialog box opens and offers users the possibility of entering a comment before the alarms are acknowledged and the Comment edit box is set to match the
    Comment
    parameter value.
  • FALSE.
    If ShowDialog = FALSE, then the
    Acknowledge Comment
    dialog box is
    not
    displayed before the selected alarms are acknowledged, using the value of the
    Comment
    parameter.
    Comment
    —
    optional parameter that controls the comment string associated with the alarm acknowledgement.
Possible errors
  • ftasErrorServerConnectionLost
  • ftasErrorInsufficientRights
  • ftasErrorGeneralFailure
  • ftasErrorUnknownAlarm
  • ftasErrorOperationIgnored
Provide Feedback
Have questions or feedback about this documentation? Please submit your feedback here.
Normal