Module Properties dialog box - Ch0x page parameters (5094-OF4IHS, 5094-OF4IHSXT)

The
Ch0x
page (5094-OF4IHS, 5094-OF4IHSXT) includes the following parameters:
Parameter
Description
Disable Channel
Select to disable channel configuration or clear to enable channel configuration.
Disable the channel to help prevent erroneous fault reporting, such as open wire fault, and to help prevent the FLT LED for that channel from illuminating.
Output Type
The output type for the channel.
Output Range
The output range for the output type.
Enable HART
Select to enable communication with HART devices.
Channel Offset
To compensate for any error in actuator operation, the module allows an offset to be added to the output channel value sent from the controller. Values are entered in Engineering Units (EU). The default value for the channel offset is 0.0.
Hold for Initialization
Select to cause the physical output to hold its present state until the value commanded by the controller matches the value at the output screw terminal within 0.1% of full scale. This feature prevents spiking of the output when transitioning into Run mode from Program mode, when recovering from a fault state, or at power up.
Off
Select to turn off the output channel.
Hold Last State
Select to cause the output to remain at the last value sent from the controller prior to being placed in Program mode and Communication Fault mode.
Engineering Units
Enter the unit of measure used for the channel.
High Signal
Enter one of four points used in scaling. The high signal is in terms of the channel signal units and corresponds to the high engineering term when scaled. The scaling equation is used.
High Signal
values must be greater than
Low Signal
values.
High Engineering
Enter one of four points used in scaling. The high engineering helps determines the engineering units the signal values scale into. The high engineering term corresponds to the high signal value. The scaling equation is used.
Low Signal
Enter one of four points used in scaling. The low signal is in terms of the channel signal units and corresponds to the low engineering term when scaled. The scaling equation is used.
Low Engineering
Enter one of four points used in scaling. The low engineering helps determines the engineering units the signal values scale into. The low engineering term corresponds to the low signal value. The scaling equation is used.
Diagnostics
Select to open the
Ch0x Diagnostics
dialog box and view diagnostic information.