Calibration Wizard - One At a Time High Reference Results parameters (5094-IRT8S, 5094-IRT8SXT, 5094-IF4IHS, 5094-IF4IHSXT, 5094-OF4IHS, 5094-OF4IHSXT)

When calibrating channels one at a time, the Calibration Wizard includes these parameters:
Parameter
Description
Channel
Shows the channel number to configure the properties for that channel.
Calibrate
Identifies the channels that were selected for calibration. Select the check box that corresponds to the channel number you want to calibrate.
Calibration Range
Shows the range currently configured for the channel. Ranges display according to the
Input Range
or
Output Range
selected.
High Reference
Shows the value of the high reference source based on the channel configuration.
Status
Shows the value read during calibration for the enabled channels.
  • If the reference signal is within the acceptable range, the status shows OK.
  • If the reference signal is not within the acceptable range, the status shows Error. Investigate the channels with errors, and then press Retry to perform calibration again on channels with errors.
Retry
Restarts the calibration for the channel.
Next
Starts the calibration of the channel.
If the value for the channel is acceptable, and another channel is selected to be calibrated, the next channel is highlighted.
Stop
Stops the calibration process.